OPERATION
4
33
IFC 100
www.krohne.com
02/2012 - 4001702901 - AD IFC 100 FF R01 en
NORMAL
Normal
R/W
This is the mode which the block should be set to during
normal operating conditions.
Auto
Setting:
Auto / OOS
ST_REV
ST_REV
ST_REV
ST_REV
Static Revision
Static Revision
Static Revision
Static Revision
R
The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.
0
Setting:
0...65535
STRATEGY
STRATEGY
STRATEGY
STRATEGY
Strategy
Strategy
Strategy
Strategy
R/W
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
0
Setting:
0...65535
TAG_DESC
TAG_DESC
TAG_DESC
TAG_DESC
Tag Description
Tag Description
Tag Description
Tag Description
R/W
The user description of the intended application of the block.
blanks
Setting:
≤32 digits
ACK_OPTION
ACK_OPTION
ACK_OPTION
ACK_OPTION
Acknowledge Option
Acknowledge Option
Acknowledge Option
Acknowledge Option
R/W
Selection of whether alarms associated with the function
block will be automatically acknowledged.
Uninitialized
Setting:
HiHi Alm Auto Ack / Hi Alm Auto Ack / LoLo Alm Auto Ack /
Lo Alm Auto Ack / Blk Alm Auto Ack/ Fail Alm Auto Ack / Off
Spec Alm Auto Ack / Maint Alm Auto Ack / Check Alm Auto Ack
ALARM_HYS
ALARM_HYS
ALARM_HYS
ALARM_HYS
Alarm Hysteresis
Alarm Hysteresis
Alarm Hysteresis
Alarm Hysteresis
R/W
Amount the PV must return within the alarm limits before the
alarm condition clears. Alarm Hysteresis is expressed as a
percent of the span of the PV.
0.5
Setting:
0...50%
ALARM_SUM
ALARM_SUM
ALARM_SUM
ALARM_SUM
Alarm Summary
Alarm Summary
Alarm Summary
Alarm Summary
The current alert status, unacknowledged states, unreported
states and disabled states of the alarms associated with the
function block.
-
CURRENT
Current
R
The active status of each alarm.
Uninitialized
Setting:
HiHi Alarm / Hi Alarm / LoLo Alarm / Lo Alarm / Block Alarm
UNACKNOWLEDGED
Unacknowledged
R
The unacknowledged state of each alarm.
Uninitialized
Setting:
HiHi Alarm Unack / Hi Alarm Unack / LoLo Alarm Unack /
Lo Alarm Unack / Block Alarm Unack
UNREPORTED
Unreported
R
The unreported status of each alarm
Uninitialized
Setting:
HiHi Alarm Unrep / Hi Alarm Unrep / LoLo Alarm Unrep /
Lo Alarm Unrep / Block Alarm Unrep
DISABLED
Disabled
R/W
The disabled state of each alarm
Uninitialized
Setting:
HiHi Alarm Disabled / Hi Alarm Disabled / LoLo Alarm
Disabled / Lo Alarm Disabled / Block Alarm Disabled
Parameter
Parameter
Parameter
Parameter
Subelement
Access
Description and settings
Initial Value