Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual

Page 33

background image

OPERATION

4

33

IFC 100

www.krohne.com

02/2012 - 4001702901 - AD IFC 100 FF R01 en

NORMAL

Normal

R/W

This is the mode which the block should be set to during

normal operating conditions.

Auto

Setting:

Auto / OOS

ST_REV

ST_REV

ST_REV

ST_REV

Static Revision

Static Revision

Static Revision

Static Revision

R

The revision level of the static data associated with the

function block. The revision value will be incremented each

time a static parameter value in the block is changed.

0

Setting:

0...65535

STRATEGY

STRATEGY

STRATEGY

STRATEGY

Strategy

Strategy

Strategy

Strategy

R/W

The strategy field can be used to identify grouping of blocks.

This data is not checked or processed by the block.

0

Setting:

0...65535

TAG_DESC

TAG_DESC

TAG_DESC

TAG_DESC

Tag Description

Tag Description

Tag Description

Tag Description

R/W

The user description of the intended application of the block.

blanks

Setting:

≤32 digits

ACK_OPTION

ACK_OPTION

ACK_OPTION

ACK_OPTION

Acknowledge Option

Acknowledge Option

Acknowledge Option

Acknowledge Option

R/W

Selection of whether alarms associated with the function

block will be automatically acknowledged.

Uninitialized

Setting:

HiHi Alm Auto Ack / Hi Alm Auto Ack / LoLo Alm Auto Ack /

Lo Alm Auto Ack / Blk Alm Auto Ack/ Fail Alm Auto Ack / Off

Spec Alm Auto Ack / Maint Alm Auto Ack / Check Alm Auto Ack

ALARM_HYS

ALARM_HYS

ALARM_HYS

ALARM_HYS

Alarm Hysteresis

Alarm Hysteresis

Alarm Hysteresis

Alarm Hysteresis

R/W

Amount the PV must return within the alarm limits before the

alarm condition clears. Alarm Hysteresis is expressed as a

percent of the span of the PV.

0.5

Setting:

0...50%

ALARM_SUM

ALARM_SUM

ALARM_SUM

ALARM_SUM

Alarm Summary

Alarm Summary

Alarm Summary

Alarm Summary

The current alert status, unacknowledged states, unreported

states and disabled states of the alarms associated with the

function block.

-

CURRENT

Current

R

The active status of each alarm.

Uninitialized

Setting:

HiHi Alarm / Hi Alarm / LoLo Alarm / Lo Alarm / Block Alarm

UNACKNOWLEDGED

Unacknowledged

R

The unacknowledged state of each alarm.

Uninitialized

Setting:

HiHi Alarm Unack / Hi Alarm Unack / LoLo Alarm Unack /

Lo Alarm Unack / Block Alarm Unack

UNREPORTED

Unreported

R

The unreported status of each alarm

Uninitialized

Setting:

HiHi Alarm Unrep / Hi Alarm Unrep / LoLo Alarm Unrep /

Lo Alarm Unrep / Block Alarm Unrep

DISABLED

Disabled

R/W

The disabled state of each alarm

Uninitialized

Setting:

HiHi Alarm Disabled / Hi Alarm Disabled / LoLo Alarm

Disabled / Lo Alarm Disabled / Block Alarm Disabled

Parameter

Parameter

Parameter

Parameter
Subelement

Access

Description and settings

Initial Value