OPERATION

4

25

IFC 100

www.krohne.com

02/2012 - 4001702901 - AD IFC 100 FF R01 en

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

Update Event

Update Event

Update Event

Update Event

R

This alert is generated by any change to the static data.

UNACKNOWLEDGED

Unacknowledged

R/W

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

UPDATE_STATE

Update State

R

A discrete enumeration which gives an indication of whether

the alert has been reported.

Uninitialized

Setting:

Uninitialized / Reported / Not reported

TIME_STAMP

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs. Time stamp records the time when parameter

was updated.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

RELATIVE_INDEX

Relative Index

R

The OD index of the static parameter whose change caused

this alert, minus the FB starting index. If the update event was

caused by a write to multiple parameters at the same time,

then this attribute will be zero.

0

Setting:

0…65535