B.139 SYSTem:PASSword:NEW COMMAND

SYST:PASS:NEW

Syntax:

Short Form: SYST:PASS:NEW ,
Long Form: SYSTem:PASSword:NEW ,

Description: Establishes new password. The old (current) Main password is checked, then replaced by the new

password. Admin 1 and 2 passwords (PAR. 3.2.4.3) are not available. (See example, Figure B-12.)
See PAR. 3.5.2.2 and Figure 3-16 for special programming considerations.

B.140 SYSTem:PASSword:STATe? QUERY

SYST:PASS:STAT?

Syntax:

Short Form: SYST:PASS:STAT?

Long Form: SYSTem:PASSword:STATe?

Return Value: 0 or 1

Description: Returns a 1 if the password state is enabled or a 0 if it is disabled.

B.141 SYSTem:REMote COMMAND

SYST:REM

Syntax:

Short Form: SYST:REM {ON | OFF} or {1 | 0}
Long Form: SYSTem:REMote {ON | OFF} or {1 | 0}

Description: Used during serial (RS 232) communication to set the unit to remote (1 or ON) or local (0 or

OFF) mode. This command must be issued prior to commands that affect the power supply output
(e.g., VOLT 10;:OUTP ON) to ensure the unit is in remote mode. See PAR. 3.5.6.3 and Figure B-11.

B.142 SYSTem:REMote? QUERY

SYST:REM?

Syntax:

Short Form: SYST:REM?

Long Form: SYSTem:REMote?

Return Value: {1 | 0}

Description: Identifies whether unit it in remote mode (1) or local mode (0) during serial (RS 232) communi-

cation. See PAR. 3.5.6.3 and Figure B-11.

FIGURE B-11. SETTING THE UNIT TO REMOTE MODE VIA SERIAL (RS 232) PORT

B.143 SYSTem:SECurity:IMMediate COMMAND

SYST:SEC:IMM

Syntax:

Short Form: SYST:SEC:IMM

Long Form: SYSTem:SECurity:IMMediate

Description: Initializes all NVRAM variable to factory defaults. Empties all memory locations. See PAR. 3.5.2.2

and Figure 3-16 for special programming considerations. This command is password protected (must
be preceded by SYST:PASS:CEN (see PAR B.137).

*IDN?

Unit responds with KEPCO,BOP 50-20,E1234,1.66 (typical).

OUTP?

Unit responds with 0 indicating output is off

SYST:REM?

Unit responds with 0 indicating unit is in local mode.

SYST:REM 1

Puts unit in remote mode.

OUTP ON

Enables output

OUTP?

Unit responds with 1 (output on).

SYST:REM 0

Unit set to local mode.