R-Series Remote Annunciators and Expanders Installation and Operation Guide

9

Figure 8: Typical annunciator wiring

(1) CH1_IN+/− from the control panel or previous annunciator. CH1_OUT+/− to the next

annunciator or to the control panel if the last annunciator on a Class A circuit.

(2) CH2_IN+/− from the control panel or previous annunciator. CH2_OUT+/− to the next

annunciator. Used only on redundant Class B circuits. See Figure 6 on page 8.

(3) Use the control panel power supply or a 24 VDC, continuous, regulated, power supply that is

UL/ULC Listed for fire protective signaling systems.

(4) To the expander. See Figure 9.

(5) The remote key switch wiring is not supervised. The key switch must be located within 3 ft.

(0.9 m) of the annunciator and installed in conduit, or equivalent protection against
mechanical injury.

A remote key switch is required on RLED-C remote annunciators.

Figure 9: Typical expander wiring

RLCD(-C) / RLED(-C)

Ch1( )_IN

Ch1( )_IN

Ch1( )_OUT

Ch1( )_OUT

24V( )_IN

24V( )_IN

24V( )_OUT

24V( )_OUT

RKEY

LOCK(+)

LOCK(- )

EGND

Ch2( )_IN

Ch2( )_IN

Ch2( )_OUT

Ch2( )_OUT

V( )_OUT

V( )_OUT

F_OUT

E_OUT

D_OUT

C_OUT

B_OUT

A_OUT

(1)

(2)

(3)

(4)

(5)

V( )_IN

V( )_OUT

V( )_IN

V( )_OUT

F_IN

F_OUT

RLED24

E_IN

E_OUT

D_IN

D_OUT

C_IN

C_OUT

B_IN

B_OUT

A_IN

A_OUT

V( )_IN

V( )_OUT

V( )_IN

V( )_OUT

F_IN

F_OUT

E_IN

E_OUT

D_IN

D_OUT

C_IN

C_OUT

B_IN

B_OUT

A_IN

A_OUT

RLED24

RLCD(-C) /

RLED(-C)