R-Series Remote Annunciators and Expanders Installation and Operation Guide
9
Figure 8: Typical annunciator wiring
(1) CH1_IN+/− from the control panel or previous annunciator. CH1_OUT+/− to the next
annunciator or to the control panel if the last annunciator on a Class A circuit.
(2) CH2_IN+/− from the control panel or previous annunciator. CH2_OUT+/− to the next
annunciator. Used only on redundant Class B circuits. See Figure 6 on page 8.
(3) Use the control panel power supply or a 24 VDC, continuous, regulated, power supply that is
UL/ULC Listed for fire protective signaling systems.
(4) To the expander. See Figure 9.
(5) The remote key switch wiring is not supervised. The key switch must be located within 3 ft.
(0.9 m) of the annunciator and installed in conduit, or equivalent protection against
mechanical injury.
A remote key switch is required on RLED-C remote annunciators.