Power switch, Power connector, 9 power switch – Detcon SmartWireless CXT User Manual
Page 13: 10 power connector
Sentinel CXT
Sentinel CXT Instruction Manual
Rev. 1.5
Page 9 of 42
Relay PCA
NC
COM
NO
FAULT
NC
COM
NO
ALARM 3
NC
COM
NO
ALARM 2
NC
COM
NO
ALARM 1
Enclosure
ALARM 2
(Green) 3
Alarm Connector
(Pin 2 is not used)
ALARM 3
(Orange) 4
FAULT
(Blue) 6
ALARM 1
(White) 1
COM
(Black) 5
1
1
2
3
4
5
6
Figure 8 External Alarm Connector Pin out for ‘Dry’ alarm contacts
1.9 Power Switch
Power to the SmartWireless® CXT is controlled by a power switch located on the bottom of the enclosure
(Figure 1). Pressing this switch while the power is off will turn the CXT on. Pressing the switch while the
power is on will turn the power off.
1.10 Power Connector
The internal battery inside the SmartWireless® CXT controller can be recharged by connecting 24VDC to
the power connector on the side of the enclosure (Figure 1). A VAC/24VDC battery charging adapter is
included with every CXT.
Detcon Approved Battery Charger Accessory Ratings:
AC Input Power
Voltage: 100-240 VAC, 50-60 Hz (requires correctly selected 110 VAC or 220 VAC Charger)
Current: 2.0 Amps maximum
DC Output Power
Voltage: 24+/- 1 VDC
Current: 3.1 Amps maximum
CAUTION
The SmartWireless® CXT must be charged with the Detcon supplied Battery
Charger. (Detcon P/N: 976-0003BC-00T for 110VAC and P/N 976-0003BC-220
for 220VAC ). Use of any other charger may damage the controller.