beautypg.com

Closed loop control mode (clc) – AW Gear Meters EMO-1005 User Manual

Page 27

background image

AW-Lake Company 8809 Industrial Drive, Franksville, WI 53126  web: www.awgearmeters.com

 Tel: 262-884-9800  Fax: 262-884-9810  Email: [email protected]

REV. 1a 05/98 EMO-1005 Manual.DOC

26

CLOSED LOOP CONTROL MODE (CLC)

The CLC mode has been adapted to the EMO-1005 for extremely slow closed loop applications. In

some applications (fluid) where the distance between the I/P converter and the regulator is more than

40 feet and the pneumatic system is not quick enough in response, the standard PI loop will not do the

job. The CLC mode has one major difference to the standard PI mode in that the corrections are done

by a percentage to the error rather than proportionally.

For example:

If a set value (Analog In) is calling for a flow rate of 20 liquid ounces but the feedback frequency is

only 18.2 liq.oz. when sending out 10mA's, then the CLC would correct the Analog Output as

follows:

Set Value - Current Value

New

Analog

Out=Old

Analog

Out

+

*

A

Set Value

where,

A is the highest value of the Analog Output. (Usually 5VDC)

After making the corrections, the CLC waits until the mellow frequency (average) catches up with the

actual frequency. After the catch-up has been achieved, within the death band limits, the CLC is then

ready for a new round of calculations.

There are a great many applications which show a lag time before any reaction in the system can be

seen. To take care of this problem, a programmable lag time factor has been added to the CLC mode.

In the CLC mode, a change at the Analog Input will immediately cause a change in the Analog

Output. Again, the change on the output is based on a percentage.

CLC Parameters

Totalizer Limit # 2

= Initial kick

(205=4mA...1023=20mA)

Totalizer Limit # 1

= Lag time

(0100 - 0255)

Sample amount

= Average

(005 -040)

Cutoff

= Death band

(100=1Hz...255=2.55Hz)

Analog In Gain

= Scales Analog

Input

The initial kick is used to start a system regulating. See the section "THE EMO-1005 PID

OPERATIONS", page 20, for more information about the initial kick.

The Cutoff is used to stop the unwanted hunting of the CLC mode. When Cutoff is set, the number in

the Cutoff is translated into a frequency. The number in the Cutoff is the margin where the EMO-1005

will stop regulating and will hold a steady Analog Output.

By increasing the Sample amount, the Lag time reaction becomes slower.

By increasing the Death band the unwanted hunting will be avoided.

** CAUTION ** Changing from one mode to another changes some of the inputs to outputs therefore,
please make sure which mode the channel card is in before hooking up external signals.