beautypg.com

Warning, Maintenance, Wiring diagrams, schematics, etc – Hired-Hand Farm Hand Series: Vent Master 24 User Manual

Page 19

background image

Part No. 4801-5124 rev 10-03

Farm Hand Vent Master 24

17
















Table 1 Example Of Cool Timer Stage Operation







Brief Description Of Cool Timer Stage Operation
As you can see, a stage will be placed on the system timer once the temperature rises above
80ºF (OFF) and will start running 50% (P71) of the time. If the temperature continues to
increase then the run time percentage will also increase toward 90% (P70).

13. Maintenance

Check the calibration of your sensors at least once per quarter. You will need to have two people: one
person at the sensor with a trusted thermometer, and one at the controller to set the sensor to the proper
setting.

14. Wiring Diagrams, Schematics, etc.

All wiring connections for stages, vent machines, variable speed fans, and
curtain sensors inside the controller are made without terminals on the end
of the wire. To make the connection, strip about ¼” of the insulation off
the wire, and follow the diagram below.

1. Insert a small screwdriver into either the hole shown in the

diagram.

2. Insert the stripped end of the wire into the hole shown in the

diagram.

3. Remove the screwdriver, and tug slightly on the wire to check that

it is snug.



Warning!

Do not connect more than 12 amps of load to any one stage. The Variable

Speed Circuit will carry up to 12 amps.

Setting

Stage Sensor

Stage Mode

Stage Timer

OffPoint

OnPoint

Cool Timer
Max %

Cool Timer
Min %

Parameter

P1 P2 P3 OFF ON P70 P71

Value

10 02 02 80

86

90 50

Option

Sensor 1

Cool Stir

Timer ON

Minimum
OnPoint

Maximum
OnPoint

Maximum
Runtime %

Minimum
Runtime %

75

80

85

90

Runtime Percentage

Graph 1 ON/Off Stages

86ºF

OnPoint

90

50

80º F

OffPoint

Temperature (F)