19
53-1002563-04
Preparing for the Brocade VDX 8770-4 installation
2
Environmental requirements
DANGER
Do not install the device in an environment where the operating ambient temperature might
exceed 40°C (104°F).
lists the environmental operating ranges for the Brocade VDX 8770-4. The requirements for
non-operating conditions are also provided for acceptable storage and transportation
environments.
NOTE
The 0
to 40
C (32
to 104
F) range applies to the ambient air temperature at the air intake vents
on the left side (as you face the port side) and port side of the Brocade VDX 8770-4.
The temperature inside the Brocade VDX 8770-4 can be up to 90°C (194
F) for some modules
during operation. Brocade recommends that the internal temperature not exceed 75°C (167
F).
Cooling policy is based on a combination of ambient temperature and measured temperature on the
modules. Various combinations will result in an increase in fan speed to create more cooling in the
switch.
If a component approaches a critical temperature that will trigger a module shutdown, there will be
a WARNING message in the RASlog, followed by a CRITICAL message saying that the module will
shut down in two minutes.
Use the show environment command to view temperature status.
TABLE 6
Environmental requirements
Condition
Acceptable range during operation
Acceptable range during non-operation
Ambient temperature
0
to 40
C (32
to 104
F) outside
switch
-25
to +70
C (-13
to 158
F) outside
switch
Humidity
5% to 90% RH noncondensing, at 40
C
(104
F), with maximum gradient of 10%
per hour
10% to 90% RH noncondensing, at 70
C
(158
F)
Altitude
0 to 3 km (10,000 ft.) above sea level
0 to 12 km (40,000 ft.) above sea level
Shock
20G, 6 ms duration, half-sine wave
33G, 11 ms duration, half-sine wave
Vibration
0.5G p-p, 5-500 Hz at 1.0 octave/minute
2.0G p-p, 5-500 Hz at 1.0 octave/minute
Airflow
Maximum: 675 cu ft/min. (1147 cu m/hr)
Nominal: 200 cu ft/min. (340 cu m/hr)
None required
Maximum heat
dissipation
Up to 6000W or 20,500 BTU/hr
Not applicable