Table 5 – Brocade VDX 8770-4 Hardware Reference Manual User Manual
Page 38
![background image](/manuals/361622/38/background.png)
18
Brocade VDX 8770-4 Hardware Reference Manual
53-1002563-04
Preparing for the Brocade VDX 8770-4 installation
2
CAUTION
For the DC input circuit to the system of a Brocade VDX 8770-4 (3000W supply), make sure there
is an 80 Amp circuit breaker, minimum -48VDC, double pole, on the input lugs to the power
supply. The input wiring for connection to the product should be copper wire, 2 AWG, marked
VW-1, and rated minimum 90
o
C.
The power requirements for a given switch configuration depend on which modules have been
installed in the switch.
shows the power consumption for the modules that can be used in
the Brocade VDX 8770-4 switch along with the power consumption for the cooling fans.
All numbers for the line cards assume that the card is fully populated with transceivers, including
QSFPs for the 12x40 GbE and 27x40 GbE line cards. All ports are Ethernet.
You can calculate your power requirements by combining the power demands for the various
modules and fan units in your configuration. While you may use fewer ports in a given line card, it is
always safer to use the power requirement of a fully populated card.
CAUTION
For the NEBS-compliant installation of a Brocade VDX 8770-4 with AC or DC systems, use a
ground wire of at least 2 AWG. The ground wire should have an agency-approved crimped
connector (provided with the device) attached to one end, with the other end attached to building
ground. The connector must be crimped with the proper tool, allowing it to be connected to both
ground screws on the enclosure. Before crimping the ground wire into the provided ground lug,
ensure that the bare copper wire has been cleaned and antioxidant is applied to the bare wire. In
addition, anti-rotation devices or lock washers must be used with all screw connections for the
grounding wire.
TABLE 5
Power demands per component
Module or fan units
Power demand at idle -
blades enabled, no
optics, ports disabled
(Watts)
Nominal power demand -
blades enabled, optics, 50%
line rate, random packets
(Watts)
Maximum power demand - blades
enabled, optics, traffic present, full line
rate, 64 byte smallest packet, 40°C
ambient temp., maximum power for all
supported optics (Watts)
Management module 46
46
50
Switch fabric module
120
120
132
48x1 Gbe line card
245
310
460
48x10 GbE line card
245
310
460
12x40 GbE line card
247
290
440
48x10G-T line card
450
665
700
27x40 GbE line card
429
489
580
6x100 GbE line card
570
611
700
Fan unit
25
25
268