beautypg.com

Power specifications, Table 4 – Brocade VDX 8770-4 Hardware Reference Manual User Manual

Page 37

background image

Brocade VDX 8770-4 Hardware Reference Manual

17

53-1002563-04

Preparing for the Brocade VDX 8770-4 installation

2

Grounded outlets installed by a licensed electrician and compatible with the power cords

DANGER

If the installation requires a different power cord than the one supplied with the device, make
sure you use a power cord displaying the mark of the safety agency that defines the regulations
for power cords in your country. The mark is your assurance that the power cord can be used
safely with the switch.

4. Plan for cable management before installing the switch.

Cables can be managed in a variety of ways, such as by routing cables below the switch, to
either side of the switch, through cable channels on the sides of the rack, or by using patch
panels.

5. Ensure that the following items are available for configuration of the Brocade VDX 8770-4:

Workstation with an installed terminal emulator, such as HyperTerminal

Console (serial) cable (provided)

Ethernet cables (not provided)

Either access to an FTP server or a Brocade USB device for backing up the switch
configuration or collecting supportsave output data (optional)

Transceivers (copper and optical) and compatible cables and direct-attach cables if
needed

6. Ensure that the air intake and exhaust vents have a minimum of 5.1 cm (2 in.) of airspace.

7. Ensure that the air temperature on the air intake side is less than 40°C (104°F) during

operation.

Power specifications

Power for the Brocade VDX 8770-4 can be supplied with either AC- or DC-based 3000 watt power
supplies. The Brocade VDX 8770-4 has room for up to four power supplies.

Table 4

shows the basic power specifications for each power supply.

.

TABLE 4

Power specifications

Specification

Value for 3000W AC power supply

Value for 3000W DC power supply

Input rating

16A

70A

Input voltage

200–240 VAC, 50-60 Hz, 16.0 Amp
maximum

-48 VDC

Operating range

180 ot 264 VAC

-40 to -60 VDC

Inrush current

Limited to 60 Amp peak for any initial
current surge or spike of 10 ms or less at
either cold or warm start. Any additional
inrush current surges or spikes in the form
of AC cycles or multiple AC cycles greater
than 10 ms and less than 150 ms, must not
exceed 25 Amp peak.

Limited to 70 Amp peak for any initial
current surge or spike of 10 ms or less at
either cold or warm start.

Output

12 VDC, 245 Amps

12 VDC, 245 Amps