beautypg.com

Yokogawa Standalone MW100 User Manual

Page 96

background image

-

96/131 -

IM MW100-S16E-1
Ed01

2.5.9. DNP client command table setting (WR)

This command is used to configure command table of DNP client. For implementing
DNP communication functions, this command is added.

WR p1, p2

(in case p2 is OFF)

24

WR p1, p2, p3, p4, p5, p6, p7, p8 (in case p2 is not OFF)


p1 : Command number (001 to 100)

p2 : Function (OFF, POLL, READ,

WRITE_SO,

WRITE_DO,

WRITE_NR)

OFF

:

Off

(do

nothing)

POLL

:

Poll

response

only

READ

:

Publish

Read

request

WRITE_SO

:

Publish

Select and Operate request

WRITE_DO :

Publish Direct Operate request

WRITE_NR :

Publish Direct Operate, NR request

p3 : Destination number (1 to 10)

p4

:

Accessing

object group number (0 to 255)

p5 : Accessing object variation number (0 to 255)

p6

:

Accessing

object index number (0 to 65535)

p7 : Top channel number to exchange data (001 to 060,

A001

to

A300,

C001

to

C300)

25

p8 : Exchanging data count (0 to 60, 0 to 300)

0 to 60 :

in case p7 is 001 to 060

0 to 300 :

in case p7 is A001 to A300 or C001 to C300

- Query

WR [p1] ?

24

Unless MATH and DNP option is specified, command can't be used.

25

When POLL or READ is set to p2, A001 to A300 can't be set to p7.