2.5.6. DNP master command table setting (WO)
This command is used to configure command table of DNP master. For implementing
DNP communication functions, this command is added.
- Setting
WO p1, p2
(in case p2 is OFF)
19
WO p1, p2, p3, p4, p5, p6, p7, p8 (in case p2 is not OFF)
p1 : Command number (001 to 100)
p2 : Function (OFF, POLL, READ,
WRITE_SO,
WRITE_DO,
WRITE_NR)
OFF
:
Off
(do
nothing)
POLL
:
Poll
response
only
READ
:
Publish
Read
request
WRITE_SO
:
Publish
Select and Operate request
WRITE_DO :
Publish Direct Operate request
WRITE_NR :
Publish Direct Operate, NR request
p3 : Destination number (1 to 10)
p4
:
Accessing
object group number (0 to 255)
p5 : Accessing object variation number (0 to 255)
p6
:
Accessing
object index number (0 to 65535)
p7 : Top channel number to exchange data (001 to 060,
A001
to
A300,
C001
to
C300)
20
p8 : Exchanging Data count (0 to 60, 0 to 300)
0 to 60 :
in case p7 is 001 to 060
0 to 300 :
in case p7 is A001 to A300 or C001 to C300
- Query
WO [p1] ?
19
Unless MATH and DNP option is specified, command can't be used.
20
When POLL or READ is set to p2, A001 to A300 can't be set to p7.