2.5.6. DNP master command table setting (WO)

This command is used to configure command table of DNP master. For implementing
DNP communication functions, this command is added.

- Setting


WO p1, p2

(in case p2 is OFF)

19

WO p1, p2, p3, p4, p5, p6, p7, p8 (in case p2 is not OFF)


p1 : Command number (001 to 100)

p2 : Function (OFF, POLL, READ,

WRITE_SO,

WRITE_DO,

WRITE_NR)

OFF

:

Off

(do

nothing)

POLL

:

Poll

response

only

READ

:

Publish

Read

request

WRITE_SO

:

Publish

Select and Operate request

WRITE_DO :

Publish Direct Operate request

WRITE_NR :

Publish Direct Operate, NR request

p3 : Destination number (1 to 10)

p4

:

Accessing

object group number (0 to 255)

p5 : Accessing object variation number (0 to 255)

p6

:

Accessing

object index number (0 to 65535)

p7 : Top channel number to exchange data (001 to 060,

A001

to

A300,

C001

to

C300)

20

p8 : Exchanging Data count (0 to 60, 0 to 300)

0 to 60 :

in case p7 is 001 to 060

0 to 300 :

in case p7 is A001 to A300 or C001 to C300

- Query

WO [p1] ?

19

Unless MATH and DNP option is specified, command can't be used.

20

When POLL or READ is set to p2, A001 to A300 can't be set to p7.