beautypg.com

Yokogawa Standalone MW100 User Manual

Page 65

background image

-

65/131 -

IM MW100-S16E-1
Ed01

Table 30. Parameters for configuring DNP application service

Kind

Configuration

Client

DNP address of the DNP client function

- configurable within 0 to 65519

Server

DNP address of the DNP server function


- configurable within 0 to 65519

Unsolicited

Message

Enabling switch for permitting unsolicited message at DNP slave/server

- toggle switch to "Enable" or not

Timestamp

Enabling switch for putting timestamp into event data at DNP slave/server


- toggle switch to "Put" or not

Relative Time

Enabling switch for using relative time as timestamp at DNP slave/server

- toggle switch to "use" or not

Select Time

Holding time of Select message at DNP slave/server


- configured within 1 to 60 [s]

Event Buffer Size

Event buffer size prepared to each object in the object table

- configurable within 1 to 100

Delay Time

Delay time from event happening to reporting

- configurable within 0 to 60 [s]

Event Count

Maximum event count contained into a single unsolicited message

- configurable within 1 to 100

Analog Deadband

Deadband applied to Analog Input and Analog Output objects

- configurable within 1 to 10000