Yokogawa Standalone MW100 User Manual
Page 65
-
65/131 -
IM MW100-S16E-1
Ed01
Table 30. Parameters for configuring DNP application service
Kind
Configuration
Client
DNP address of the DNP client function
- configurable within 0 to 65519
Server
DNP address of the DNP server function
- configurable within 0 to 65519
Unsolicited
Message
Enabling switch for permitting unsolicited message at DNP slave/server
- toggle switch to "Enable" or not
Timestamp
Enabling switch for putting timestamp into event data at DNP slave/server
- toggle switch to "Put" or not
Relative Time
Enabling switch for using relative time as timestamp at DNP slave/server
- toggle switch to "use" or not
Select Time
Holding time of Select message at DNP slave/server
- configured within 1 to 60 [s]
Event Buffer Size
Event buffer size prepared to each object in the object table
- configurable within 1 to 100
Delay Time
Delay time from event happening to reporting
- configurable within 0 to 60 [s]
Event Count
Maximum event count contained into a single unsolicited message
- configurable within 1 to 100
Analog Deadband
Deadband applied to Analog Input and Analog Output objects
- configurable within 1 to 10000