Table 10. Parameters for configuring polling period and action

Kind

Configuration

Integrity Poll

Period and publishing commands for polling static data

- period is configurable within 1 to 3600 [s]

- class read :


- selectable from “Off”, “Class 0”, “Class 0, 1, 2, 3”

- command publishing :

- Max. 100 entries

Event Poll

Period and publishing commands for polling event data

- period is configurable within 1 to 3600 [s]


- class read

- selectable from “Off”, “Class 1, 2, 3”, “Class 0, 1, 2,3”

Response

Timeout

Limit of waiting time for the response corresponding to the command


- configurable within 1 to 60 [s]

- When response is not received over the limit,