Ed01
Responded variations to event polls are shown in Table 25. When event data are read
with variation zero, DNP slave/server functions will respond with the same data type
to the default variation with putting timestamp information as needed.
Table 25. Responded variations to event poll
8
Object
requested
variation
default
variation
Put time
stamp
Use relative
time
Responded
variation
Binary Input Event (2)
0 (zero)
-
No
-
1
Yes
No
2
Yes
3
none-0
- - - Requested
variation
Binary Output Event (11) 0 (zero)
-
No
-
1
Yes
-
2
none-0
- - - Requested
variation
Analog Input Event (32)
0 (zero)
1, 3
No
-
1
Yes
-
3
2,
4
No
-
2
Yes
-
4
5
No
-
5
Yes
-
7
6
No
-
6
Yes
-
8
none-0
- - - Requested
variation
Analog Output Event (42) 0 (zero)
1
No
-
1
Yes
-
3
2
No
-
2
Yes
-
4
3
No
-
5
Yes
-
7
4
No
-
6
Yes
-
8
none-0
- - - Requested
variation
'-' shows don't care
8
When objects are read via Class object, responded variation will be the same like as read
with variation 0.