beautypg.com

Yokogawa Standalone MW100 User Manual

Page 35

background image

-

35/131 -

IM MW100-S16E-1
Ed01

Framework of data mapping between DNP objects and MW100 channels in DNP
slave/server functions is shown in Figure 24 and Table 15. In MW100, index number
assigned to each channel is fixed regardless of the destination object types.

Figure 18. Data mapping between DNP objects and MW100 channels

Binary Input (1),

Analog Input (30),

0 to 59

0 to 59

Binary Input (1),

Analog Input (30),

1000 to 1299

Binary Output (10),

Analog Output (40),

2000 to 2299

2000 to 2299

1000 to 1299

I/O channel
(001 to 060)

Math channel

(A001 to A300)

Comm. Input channel

(C001 ∼ C300)

I/O

Compute

DNP objects

MATH)

Binary Output (10),

Analog Output (40),

0 to 59

0 to 59

MW100 channels