Table 35. Parameters for configuring object table

Kind

Configuration

Channel Top

Top channel of MW100 which show data with DNP objects

- selectable within 001 to 060, A001 to A300 or C001 to C300

Channel Count

Channel count of MW100 which show data with DNP objects


- configurable within :

1 to 60 when 001 to 060 is set to top channel,

1 to 300 when 'A' or 'C' channel is set to top channel

Event Class

Event class assigned to the DNP objects

- selectable from ”None”, “Class 1”, “Class 2”, “Class 3”

Default Variation

Default variation to reply to the request with variation 0


- In case of Binary Input, Binary Output objects, selectable from :

- 1 (Packed Bit)

-

2

(Flag)

- In case of Analog Input objects, selectable from :


- 1 (Int 32 with Flag)

- 2 (Int 16 with Flag)

- 3 (Int 32)

- 4 (Int 16)

- 5 (Short Float with Flag)

- 6 (Long Float with Flag)

- In case of Analog Output objects, selectable from :

- 1 (Int 32 with Flag)

- 2 (Int 16 with Flag)

- 3 (Short Float with Flag)