Warning, Combustion air and vent system requirements – A.O. Smith 12 40GPC T 100 User Manual

Page 7

background image

7

COMBUSTION AIR AND VENT SYSTEM REQUIREMENTS

Table 1:

BTUH Input

Minimum Square

Feet with

8’ Ceiling

Typical Room

with 8’ Ceiling

30,000

188

9 x 21

45,000

281

14 x 20

60,000

375

15 x 25

75,000

469

15 x 31

90,000

563

20 x 28

105,000

657

20 x 33

120,000

750

25 x 30

135,000

844

28 x 30

IMPORTANT:
• The area must be open and be able to provide

the proper air requirements to the water

heater. Areas that are being used for storage

or contain large objects may not be suitable

for water heater installation.

• Water heaters installed in open spaces in

buildings with unusually tight construction may

still require outdoor air to function properly. In

this situation, outside air openings should be

sized the same as for a confined space.

• Modern home construction usually requires

supplying outside air into the water heater

area.

• Room exhaust fans may effect air

requirements.

Confi ned Space: For the correct and proper

operation of this water heater, ample air must be

supplied for the combustion, ventilation, and dilu-

tion of fl ue gases. Small enclosures and confi ned

areas must have two permanent openings so that

suffi cient fresh air can be drawn from outside of

the enclosure. One opening shall be within 12

inches of the top and one within 12 inches of the

bottom of the enclosure.

The size of each opening (free area) is deter-

mined by the total BTUH input of all gas utilization

equipment (i.e., water heaters, furnaces, clothes

dryers, etc.) and the method by which the air is

provided. The BTUH input can be found on the

water heater rating plate. Additional air can be

provided by two methods:

1. All air from inside the building.
2. All air from outdoors.

CLOSET

OR

OTHER

CONFINED

SPACE

12” MAXIMUM

PERMANENT

OPENINGS TO

THE OUTSIDE OR

ADDITIONAL

ROOMS WITHIN

THE BUILDING

12” MAXIMUM

Combustion Air Requirements:

WARNING

Carbon Monoxide Warning

Water heater must be vented to outdoors.
Vent must be installed by a qualified technician using
the local and state codes or, in the absence of local
and state codes, the National Fuel Gas Code,
ANSI Z223.1 (NFPA 54) - current edition, and/or the
installation instructions.
Examples of a qualified technican include: gas
technicians, authorized gas company personel, and
authorized service persons.
Failure to so do can result in death or carbon monoxide
poisoning.

IMPORTANT: Air for combustion and ventilation

must not come from a fl ammable or corrosive at-

mosphere. Any failure due to fl ammable or corro-

sive elements in the atmosphere is excluded from

warranty coverage.

The following types of installation (not limited to

the following) will require outdoor air for combus-

tion due to chemical exposure and may reduce

but not eliminate the presence of corrosive chemi-

cals in the air:

• beauty

shops

• photo processing labs

• buildings with indoor pools

• water heaters installed in laundry, hobby, or

craft rooms

• water heaters installed near chemical storage

areas

• water

softeners

Combustion air must be free of acid-forming

chemicals such as sulfur, fl uorine, and chlorine.

These elements are found in aerosol sprays, de-

tergents, bleaches, cleaning solvents, air freshen-

ers, paint, and varnish removers, refrigerants, and

many other commercial and household products.

When burned, vapors from these products form

highly corrosive acid compounds. These prod-

ucts should not be stored or used near the water

heater, air inlet, or air intake path.

Combustion and ventilation air requirements are

determined by the location of the water heater.

The water heater may be located in either an

open (unconfi ned) area or in a confi ned area or

small enclosure such as a closet or small room.

Confi ned spaces are areas with less than 50 cubic

feet for each 1,000 BTUH of the total input for all

gas-using appliances.

Unconfi ned Space: A water heater in an uncon-

fi ned space uses indoor air for combustion and

requires at least 50 cubic feet for each 1,000

BTUH of the total input for all gas appliances. The

table below shows a few examples of the mini-

mum square footage (area) required for various

BTUH inputs.