Reinstalling The Inner Door/Manifold/Burner Assembly
17. Insert the manifold/burner assembly in the burner

chamber compartment, making sure that the tip

of burner manifold tab engages in the slot of the

bracket (Figure 107).

The tip end of the burner manifold MUST

be placed in the slotted portion under the

condensation pan to obtain proper installation

(Figure 107).

18. After confirming no material of any type are

between door gasket and combustion chamber

shield, align the screws on the inner door with

the screw holes on the combustion chamber and

tighten with 1/4” nut driver or 1/4” socket & ratchet

(Figure 106). After tightening the inner door

screws, visually inspect area around door

gasket and skirt for spaces or gaps. The door

gasket MUST be sealed completely in order

for the water heater to perform properly.

DO NOT OPERATE THE WATER HEATER IF

THE DOOR GASKET DOES NOT CREATE

A SEAL BETWEEN MANIFOLD DOOR AND

COMBUSTION CHAMBER.

19. Reconnect the manifold tube to the gas control

valve/thermostat (Note: Do Not apply any thread

sealant at this connection). To prevent any cross

threading the manifold tube should be started

by hand (turn clockwise -natural gas). Upon

tightening with the fingers and confirming it has

not been cross threaded, tighten nut with an 3/4”

open end wrench or crescent wrench (Figure 110).

20. Reconnect all the electrical connections to the

bottom of the gas control valve/thermostat, gently

pushing each connector up snapping into place

(Figure 110).

21. Reconnect the electrical flag terminals and air

pressure tubing to pressure switch (Figure 111).

22. Turn on the electrical and the gas supplies to the

water heater. Plug in the electric connection from

the transformer to the electric outlet (Figure 103).

23. Restart the water heater by following the

directions on the “Lighting and Operating

Instructions” label located on the front of the water

heater.

24. As the burner is heating (view flames through

viewport), test the manifold tube connection at

the gas control valve/thermostat by brushing on

an approved noncorrosive leak detection solution

(IMPORTANT: Do Not splash any solution onto

any electrical connections) (Figure 110).

25. Upon verifying proper operation of the water

heater, replace the manifold cover/outer door.

IMPORTANT:

WHEN BRUSHING ON AN
APPROVED NONCORROSIVE
LEAK DETECTION SOLUTION,
DO NOT SPLASH SOLUTION
ONTO ELECTRICAL CON-
NECTIONS.

IGNITER/
FLAME
SENSE
CONNECTOR

MANIFOLD TUBE

POWER SUPPLY
TRANSFORMER
CONNECTOR

PRESSURE
SWITCH/FAN,
FV SENSOR
CONNECTOR

DISPLAY, ANODE
ROD CONNECTOR

GAS CONTROL
VALVE/THERMOSTAT

Figure 110.

Figure 111.

PRESSURE
SWITCH

MANIFOLD
TUBE