Checking the gas supply pressure, If . . . . . . then – A.O. Smith 12 40GPC T 100 User Manual

Page 52

background image

52

23. Turn on the gas supply to the unit and test the gas

supply line and union connections by brushing on

an approved noncorrosive leak detection solution

(Figure 116).

24. Turn on the electrical and the gas supplies to the

water heater. Plug in the electric connection from

the transformer to the electric outlet (Figure 113).

25. Restart the water heater by following the

directions on the “Lighting and Operating

Instructions” label located on the front of the water

heater .

26. As the burner is heating (view flames through

viewport), test the manifold tube connection at

the gas control valve/thermostat by brushing on

an approved noncorrosive leak detection solution

(IMPORTANT: Do Not splash any solution onto

any electrical connections) (Figure 120).

27. Upon verifying proper operation of the water

heater, replace the manifold cover/outer door.

IMPORTANT:

WHEN BRUSHING ON AN
APPROVED NONCORROSIVE
LEAK DETECTION SOLUTION,
DO NOT SPLASH SOLUTION
ONTO ELECTRICAL CON-
NECTIONS.

IGNITER/
FLAME
SENSE
CONNECTOR

MANIFOLD TUBE

POWER SUPPLY
TRANSFORMER
CONNECTOR

PRESSURE
SWITCH/FAN,
FV SENSOR
CONNECTOR

DISPLAY, ANODE
ROD CONNECTOR

GAS CONTROL
VALVE/THERMOSTAT

Figure 120.

Checking the Gas Supply Pressure

Gas pressure checks are done with flowing gas

using a gas pressure gauge capable of reading

pressure in inches of water column.

GAS

PRESSURE

GAUGE

CONNECTED AT

PRESSURE TAP

GAS CONTROL

VALVE/

THERMOSTAT

SUPPLY GAS PRESSURE TEST

USE AN ALLEN

WRENCH TO REMOVE

AND REPLACE PLUG.

GAS CONTROL

VALVE/

THERMOSTAT

MANIFOLD GAS PRESSURE TEST

IF . . .

. . . THEN

supply gas pressure is under desired pressure
requirement

increase supply gas pressure regulator setting

and,

increase supply gas piping size.

supply gas pressure is over desired pressure

add gas pressure regulator.

reduce setting on existing regulator.

manifold gas pressure is more than +/- .3 inch
W.C. from values indicated on gas valve

ensure there is adequate supply gas pressure

ensure the main burner orifi ce is the correct size
for the water heater model being tested.

if the above tests have been performed and the
results were correct replace the gas control valve.

Figure 121

Supply gas pressure checks are measured
before the gas control valve/thermostat and
as close to the water heater as possible.

Manifold (main burner) gas pressure is
measured at the pressure tap on the side
of the gas control valve/thermostat. Use
an allen wrench to remove the plug then
attach the gas gauge.

NOTE: Desired gas pressures will be noted on

the gas valve label located on the gas control

valve/thermostat.

CHECKING THE GAS SUPPLY PRESSURE