with the machine stationary. Check that the
“Power” indicators on both the MCS-166
and MCS-208 are illuminated.
4. Set the front panel “Torque/Span Adjust”
potentiometer to its full CCW positioning.
5. Brake-off/brake-on switch checks
a. Set the brake-on switch to its normal
run mode.
b. Set brake-off switch to off position
and note the transducer pressure.
c. Return the brake-off switch to its
normal running position.
d. Place the brake-on switch (if used) in
the brake-on position and note that
the transducer pressure output
increases.
e. Return the brake-on switch to its
normal running position.
NoTe: If the transducer pressure decreases when
brake-on is activated, the wiring is reversed. Refer to
the MCS-208 wiring section for the proper connections.
6. Brake Off/Brake On Calibration
NoTe: The MCS-208 is factory calibrated for a 4-20ma
output. Proceed to Step 7, Transducer Calibration, if
the MCS-208 need not be adjusted. If adjustment is
required, refer to Table 2 for the correct values called
out in the adjustment procedure. An accurate voltmeter
is required to set up the system.
Table 2
Y min (Min transducer input)
Y max (Max transducer input)
P sup (supply pressure)
P max (max pressure - brake-on mode)
P cal (max pressure - run mode)
* For current transducers, this value is given in maDC.
For voltage transducers, this value is given in VDC.
** If shop air does not maintain 80 psi minimum, the P
max and P cal should be set lower. P max should be at
least 5 psi lower than the minimum supply pressure. P
sup and P cal should be at least 5 psi less than P max.
a. With the control power off, set the
meter to measure MCS-208 control
output to the transducer.
b. Apply power to the system.
c. Place the brake-off switch in the
brake-off mode.
d. Set the zero potentiometer on the
control output driver board to Y min.
(Refer to Table 2). Rotate the zero
potentiometer CW to increase and
CCW to decrease the output.
e. Return the brake-off switch to normal
run mode.
f. Set the brake-on switch to the brake
on mode.
g. Set the span potentiometer on the
control output driver board to equal Y
max. Rotate the span pot CW to
increase and CCW to decrease the
output.
h. Return the brake-on switch to the
normal run mode.
i. Repeat Steps c-h to make sure the
zero and span potentiometers are
properly set. There is some
interaction between these two
potentiometers.
7. Transducer Calibration
NoTe: For transducers that are precalibrated for
0-75 psi, calibration is not generally required. If the
transducer is labeled as calibrated for 0-75 psi and is
mounted vertically, proceed to Section C, Input
Calibration. Otherwise proceed with the following
adjustment procedure. The zero and span potentiome-
ters are identified on the outside of the transducer.
Use care when adjusting these potentiometers.
a. Place the brake-off switch in the
brake-off mode.
b. If the pressure reads above 0 psig,
turn the zero pot on the transducer
CCW until the pressure just reaches
zero.
Transducer Range
Adjustment
1-5
4-20
10-50
1-5
1-9
Variable
(ma DC)
(ma DC)
(ma DC)
(VDC)
(VDC)
Y min*
1
4
10
1
1
Y max*
5
20
50
5
9
P sup** (psi)
80
80
80
80
80
P max** (psi)
75
75
75
75
75
P cal** (psi)
70
70
70
70
70