with the machine stationary. Check that the
“Power” indicators on both the MCS-166
and MCS-208 are illuminated.

 4. Set the front panel “Torque/Span Adjust”

potentiometer to its full CCW positioning.

 5. Brake-off/brake-on switch checks

 a. Set the brake-on switch to its normal

run mode.

 b. Set brake-off switch to off position

and note the transducer pressure.

 c. Return the brake-off switch to its

normal running position.

 d. Place the brake-on switch (if used) in

the brake-on position and note that
the transducer pressure output
increases.

 e. Return the brake-on switch to its

normal running position.

NoTe: If the transducer pressure decreases when
brake-on is activated, the wiring is reversed. Refer to
the MCS-208 wiring section for the proper connections.

 6. Brake Off/Brake On Calibration

NoTe: The MCS-208 is factory calibrated for a 4-20ma
output. Proceed to Step 7, Transducer Calibration, if
the MCS-208 need not be adjusted. If adjustment is
required, refer to Table 2 for the correct values called
out in the adjustment procedure. An accurate voltmeter
is required to set up the system.

Table 2

Y min (Min transducer input)
Y max (Max transducer input)
P sup (supply pressure)
P max (max pressure - brake-on mode)
P cal (max pressure - run mode)

* For current transducers, this value is given in maDC.
For voltage transducers, this value is given in VDC.

** If shop air does not maintain 80 psi minimum, the P
max and P cal should be set lower. P max should be at
least 5 psi lower than the minimum supply pressure. P
sup and P cal should be at least 5 psi less than P max.

 a. With the control power off, set the

meter to measure MCS-208 control
output to the transducer.

 b. Apply power to the system.
 c. Place the brake-off switch in the

brake-off mode.

 d. Set the zero potentiometer on the

control output driver board to Y min.
(Refer to Table 2). Rotate the zero
potentiometer CW to increase and
CCW to decrease the output.

 e. Return the brake-off switch to normal

run mode.

 f. Set the brake-on switch to the brake

on mode.

 g. Set the span potentiometer on the

control output driver board to equal Y
max. Rotate the span pot CW to
increase and CCW to decrease the
output.

 h. Return the brake-on switch to the

normal run mode.

 i. Repeat Steps c-h to make sure the

zero and span potentiometers are
properly set. There is some
interaction between these two
potentiometers.

 7. Transducer Calibration

NoTe: For transducers that are precalibrated for
0-75 psi, calibration is not generally required. If the
transducer is labeled as calibrated for 0-75 psi and is
mounted vertically, proceed to Section C, Input
Calibration. Otherwise proceed with the following
adjustment procedure. The zero and span potentiome-
ters are identified on the outside of the transducer.
Use care when adjusting these potentiometers.

 a. Place the brake-off switch in the

brake-off mode.

 b. If the pressure reads above 0 psig,

turn the zero pot on the transducer
CCW until the pressure just reaches
zero.

Transducer Range

Adjustment

1-5

4-20

10-50

1-5

1-9

Variable

(ma DC)

(ma DC)

(ma DC)

(VDC)

(VDC)

Y min*

1

4

10

1

1

Y max*

5

20

50

5

9

P sup** (psi)

80

80

80

80

80

P max** (psi)

75

75

75

75

75

P cal** (psi)

70

70

70

70

70