Vanguard TRM-20_40 User Manual
Page 45
![background image](/manuals/354190/45/background.png)
REV 1 TRM-20 AND TRM-40 USER’S MANUAL
41
p. After saving the readings, the following screen will be displayed:
Set the LTC or Voltage Regulator tap position to the position indicated on the LCD screen
and press the
[START]
key.
The TRM will continue the test and display the results as in step n. Repeat steps l
through o for all “Lower” positions and then through all “Raise” positions.
q. The following screen will be displayed after the last “Raise” position’s resistance reading
is stored:
1. YES
Press the
[1]
key (YES) to print the test results on the built-in thermal printer. A
Typical LTC/Voltage Regulator test report is shown in Figure 6. Continue to step
r.
2. NO
Press the
[2]
key (NO) to bypass printing of the test results. Continue to step r.
r. The following screen will be displayed:
1. YES
Press the
[1]
key (YES) to save the test record. The following screen will be
displayed:
SAVE THIS RECORD?
1. YES
2. NO
PRINT RECORD?
1. YES
2. NO
set tap to 2 lower
("START" to CONTINUE)
** XFMR ENERGIZED! **