Tb1 relay 1, N.c. com, Relay 2 com n.c – KB Electronics KBDA-42 User Manual
Page 54: Relay 1 relay 2
53
A12. MULTI-FUNCTION OPEN COLLECTOR OUTPUTS
Two Open Collector Outputs are provided, which can be programmed for Run, Fault, Target
Frequency, Frequency Threshold Level (> 8.04 – 8.05), Frequency Threshold Level (< 8.04 + 8.05), I2t
or I•t Fault, Load Loss, External Fault, and Motor Overload. Open Collector Output 1 is factory pro-
grammed to operate as a Target Frequency indicator (Function No. 8.02 set to “0002” (factory set-
ting)). Open Collector Output 2 is factory programmed to operate as a Frequency Threshold Level
(< 8.04 + 8.05) indicator (Function No. 8.03 set to “0004” (factory setting)). See Figure 39, on page 54.
See Table 17, on page 54, for the Multi-Function Open Collector Output electrical Ratings.
Multi-Function Open Collector Output 1
Collector (O.C.): TB1 Terminal “11”.
Emitter (COM): TB1 Terminal “12” (internal circuit common).
Multi-Function Open Collector Output 2
Collector (O.C.): TB1 Terminal “13”.
Emitter (COM): TB1 Terminal “14” (internal circuit common).
Multi-Function Output Relay 2 Contacts
Normally Open (N.O.) Contact: TB1 Terminal “26”.
Common (COM): TB1 Terminal “27” (contact common for Relay 2 only).
Normally Closed (N.C.) Contact: TB1 Terminal “28”.
FIGURE 38 – MULTI-FUNCTION OUTPUT RELAY CONTACTS CONNECTIONS AND FUNCTION SETTINGS
14
4
16
15
1
17
2
3
18
TB1
Relay 1
9
21
5
19
6
20
N.O.
22
7
23
8
N.O.
26
N.C.
COM
10
24
11
25
Relay 2
COM N.C.
27
12
28
13
Relay 1
Relay 2
Function Settings
Function No.
Code
8.00
Multi-Function
Output Relay 1
0000 – 0008
Run, Fault, Target Frequency,
Frequency Threshold Level
(> 8.04 – 8.05),
Frequency Threshold Level
(< 8.04 + 8.05), I2t or I•t
Fault, Load Loss, External
Fault, Motor Overload
8.00
Multi-Function
Output Relay 2
0000 – 0008
Run, Fault, Target Frequency,
Frequency Threshold Level
(> 8.04 – 8.05),
Frequency Threshold Level
(< 8.04 + 8.05), I2t or I•t
Fault, Load Loss, External
Fault, Motor Overload