Function group 1 – run/stop mode – KB Electronics KBDA-42 User Manual
Page 34
33
Function
No.
Description
Range/Code
Factory
Setting
1.00*
Run/Stop-Forward/Reverse Control
0000: Keypad
0001: External Contacts
(1)
0002: Communication
(2)
0000
1.01*
Forward/Reverse Control
0000: Instant Reverse
0001: Stop Command Must be Given
Prior to Reverse Command
0002: Reverse Command Disabled
0003: Forward Command Disabled
0000
1.02*
Motor Direction
0000: Forward
0001: Reverse
0000
1.03*
Start Command
0000: Accelerates to Last Set Frequency
0001: Accelerates to Lower Frequency Limit
(See Function No. 3.01)
0000
1.04*
Start Mode
0000: Spin Start
0001: Stop Before Restart
0000
1.05*
Auto/Manual Start Mode
0000: Manual Start Mode
0001: Manual Start with Ride-Through
(Set by Function No. 1.06)
0002: Auto Start After Undervoltage Fault Clears
0003: Auto Start All Faults (Except Short Circuit Fault)
(3)
0004: Auto Start All Faults
(Except I2t , I•t, and Short Circuit Faults)
0000
1.06*
Ride-Through Time (Seconds)
0.0 – 2.0
0.5
1.07*
Number of Restart Attempts
0 – 10
3
1.08*
Auto Start Delay Time (Seconds)
0 – 240
0
1.09*
Stop Mode
0000: Regenerate-to-Stop
0001: Coast-to-Stop
0002: Regeneration with Injection Brake-to-Stop
(Set by Function Nos. 1.11 – 1.13)
0000
1.10*
Holding Torque in Stop Mode (%)
0 – 10
1
1.11
*
Injection Brake Start Frequency (Hz)
0.00 – 240.0
0.00
1.12
*
Injection Brake Level (%)
0 – 30
0
1.13
*
Injection Brake Time (Seconds)
0.0 – 25.5
0.0
FUNCTION GROUP 1 – RUN/STOP MODE
Notes: (1) IODA Option Board required. (2) DIAC Option Board required. (3) For Auto Start, Function No. 1.07 must be set to greater than “0”.
* Functions which can only be changed while the drive is in the Stop Mode.