Start, 0 - ±5 volts dc v, Other functions and features of the ioda – KB Electronics KBDA-42 User Manual
Page 50
49
A8.
SIGNAL FOLLOWING
An analog voltage (unidirectional or bidirectional), current, or PWM signal input can be used to control
motor speed in lieu of the Keypad or the Built-In Potentiometer. The drive output will linearly follow the
signal input. The inputs can be programmed for the desired gain, slope, offset, and response time.
See Analog Input Signal Operation (Function Group 9).
Analog Input 1 – Connect the signal input to Terminal “19” and the common to Terminal “20”, as
shown in Figure 34. See settings for Analog Input 1 (Function Nos. 9.00 – 9.04). Set Frequency
Control (Function No. 2.00) to Analog Input 1 (“0002”). For unidirectional voltage input, set Analog
Input 1 Type (Function No. 9.03) to Unidirectional ((“0000”) (factory setting)). For bidirectional voltage
input, set Function No. 9.03 to Bidirectional (“0001”). See Table 14, on page 50, for Analog Input 1
electrical ratings.
If the Analog Input 1 signal is higher than 5 Volts, use Trimpot MAX1 to attenuate it. Apply the maxi-
mum signal input and set the drive for full speed output and observe the display. Rotate Trimpot
MAX1 counterclockwise until the drive output frequency begins to drop. Then rotate Trimpot MAX1
clockwise until the display returns to the maximum output frequency.
FIGURE 33 – 3-WIRE START/STOP SWITCH OR CONTACT CONNECTION AND FUNCTION SETTINGS
1
Start
15
TB1
Stop
Momentarily close the Start Switch or Contact to run the drive.
Momentarily open the Stop Switch or Contact to stop the drive.
3
2
16
17
5
4
18
19
7
6
20
21
9
8
22
23
28
11
10
24
25
13
12
27
26
14
Function Settings
Function No.
Code
1.00
Run/Stop-Forward/Reverse
Control
0001
External
Contacts
7.00
Multi-Function
Input Terminal 1
0010
Normally Open
Start
7.01
Multi-Function
Input Terminal 2
0011
Normally Closed
Stop
FIGURE 34 – ANALOG INPUT 1 SIGNAL VOLTAGE FOLLOWING CONNECTION AND FUNCTION SETTINGS
-
+
14
4
16
15
1
TB1
18
17
2
3
9
21
20
19
5
6
23
22
7
8
26
25
24
10
11
28
27
12
13
0 - ±5 Volts DC
V
MAX1
Function Settings
Function No.
Range/Code
2.00
Frequency
Control
0002
Analog
Signal 1
9.00
Analog Input 1
Gain
0 – 500
Set to the
Desired Gain
9.01
Analog Input 1
Slope
0000 or 0001
Positive or
Negative
9.02
Analog Input 1
Offset
0 – 100
Set to the
Desired Offset
9.03
Analog Input 1
Type
0000 or 0001
Unidirectional or
Bidirectional
9.04
Analog Input 1
Response Time
2 – 100
Set to the
Desired Time
OTHER FUNCTIONS AND FEATURES OF THE IODA