KB Electronics KBDA-42 User Manual
Page 38
37
Function
No.
Description
Range/Code
Factory
Setting
8.00*
Multi-Function Output Relay 1
(Terms. 23 – 25)
0000: Run
0001: Fault
(1)
0002: Target Frequency
(Function No. 8.04 ± Function No. 8.05)
0003: Frequency Threshold Level
(> Function No. 8.04 – Function No. 8.05)
(2)
0004: Frequency Threshold Level
(< Function No. 8.04 + Function No. 8.05)
(3)
0005: I2t or I•t Fault
0006: Load Loss (See Function No. 5.03)
0007: External Fault
0008: Motor Overload
(4)
0000
8.01*
Multi-Function Output Relay 2
(Terms. 26 – 28)
0001
8.02*
Multi-Function Open Collector Output 1
(Terms. 11, 12)
0002
8.03*
Multi-Function Open Collector Output 2
(Terms. 13, 14)
0004
8.04
*
Frequency Set Point (Hz)
0.00 – 240.0
0.00
8.05
*
Frequency Bandwidth (± Hz)
0.00 – 30.00
1.00
8.06
*
Analog Output 1 Mode (Terms. 15, 16)
(0 – 5 VDC)
0000: Motor Frequency
0001: Set Frequency
0002: Motor Voltage
0003: Bus Voltage
0004: Motor Current
0000
8.07
*
Analog Output 1 Gain (%)
0 – 200
100
8.08
*
Analog Output 2 Mode (Terms. 17, 18)
(See Function No. 8.09)
0000: Motor Frequency
0001: Set Frequency
0002: Motor Voltage
0003: Bus Voltage
0004: Motor Current
0000
8.09
*
Analog Output 2 Type
(5)
0000: 0 – 5 VDC
0001: 0 – 20 mA DC
0002: 4 – 20 mA DC
0000
8.10
*
Analog Output 2 Gain (%)
0 – 200
100
FUNCTION GROUP 8 – MULTI-FUNCTION OUTPUT RELAYS AND
OUTPUT SIGNAL OPERATION (IODA OPTION BOARD REQUIRED)
Notes: (1) The Multi-Function Output Relays and Open Collector Outputs will change state due to all Faults and Recovered Faults. (2) The
relay will activate above the setting in 8.04 and deactivate below the setting of 8.04 – 8.05. (3) The relay will activate below the setting in
8.04 and deactivate above the setting of 8.04 + 8.05. (4) The Output Relay will change state when the I
2
t or I•t Timer starts. (5) Analog
Output 2 Type: For 0 – 5 VDC (code “0000”), set Jumpers J2 and J3, on the IODA, to the “VOLT” Position (factory setting). For 0 – 20 mA DC
(code “0001”) or 4 – 20 mA DC (code “0002”), set Jumpers J2 and J3, on the IODA, to the “CUR” position.
*Functions which can only be changed while the drive is in the Stop Mode.