Function group 4 – digital display modes – KB Electronics KBDA-42 User Manual
Page 36
35
Function
No.
Description
Range/Code
Factory
Setting
4.00
Display Mode
0000: Frequency
0001: RPM
(1)
0002: Custom Units
0000
4.01
Custom Units Significant Digits
0 – 9999
100
4.02
Custom Units Display
0000: Whole Numbers
0001: One Decimal Place
0002: Two Decimal Places
0003: Three Decimal Places
0000
4.03
Display in Stop Mode
0000: Displays Last Run Setting
0001: Displays “StoP”
0002: Displays “0000”
0000
4.04
Motor Current Display
(2), (3)
0000: Disabled
0001: Enabled
0000
4.05
Motor Voltage Display
(2), (3)
0000: Disabled
0001: Enabled
0000
4.06
Bus Voltage Display
(2), (3)
0000: Disabled
0001: Enabled
0000
FUNCTION GROUP 4 – DIGITAL DISPLAY MODES
Notes: (1) Based on 4-pole motor. (2) The Display Key is used to toggle between displays. See Figure 22, on page 29. (3) If Motor Current
Display is enabled, the display will show “XX.XA”. If Motor Voltage Display is enabled, the display will show “XXXu”. If Bus Voltage Display is
enabled, the display will show “XXXU”.
Function
No.
Description
Range/Code
Factory
Setting
5.00
Relay Operation Mode
0000: Run
0001: Fault
(1)
0002: Target Frequency
(Function No. 5.01 ± Function No. 5.02)
0003: Frequency Threshold Level
(> Function No. 5.01 – Function No. 5.02)
(2)
0004: Frequency Threshold Level
(< Function No. 5.01 + Function No. 5.02)
(3)
0005: I2t or I•t Fault
0006: Load Loss (See Function No. 5.03)
0000
5.01
Frequency Reached (Hz)
0.00 – 240.0
0.00
5.02
Frequency Bandwidth (Hz)
0.00 – 30.00
1.00
5.03
Load Loss Threshold
(4)
(% Motor Current, set by 0.01)
25 – 90
60
FUNCTION GROUP 5 – ONBOARD MULTI-FUNCTION OUTPUT RELAY OPERATING MODE
Note: (1) The Output Relay contacts will change state due to all Faults and Recovered Faults. (2) The relay will activate above the setting in
Function No. 5.01 and deactivate below the setting in Function No. 5.01 minus the setting in Function No. 5.02. (3) The relay will activate
below the setting in Function No. 5.01 and deactivate above the setting in Function 5.01 plus the setting in Function No. 5.02. (4) The Load
Loss Threshold function is not functional during acceleration/deceleration or Stop Mode.