6.2
GROUND CONNECTION – Connect the ground wire (earth) to any available green Ground Screw.
The two Ground Screws are located near Terminal Block TB1. Be sure the motor is also properly
grounded. See Figure 10, on page 18, and Figure 11, above.
6.3
MOTOR CONNECTION – Connect the motor to Terminal Block TB1 Terminals “U”, “V”, “W”. See
Figure 10, on page 18, and Figure 11, above. Be sure the motor is properly grounded. Motor cable
length should not exceed 100 ft. (30 m) – special reactors may be required – consult our Sales
Department. Be sure Function No. 0.01 is set to the corresponding Motor Nameplate Current.
Note: If the motor does not rotate in the desired direction, either: 1. Reverse any two motor leads
(with AC line disconnected and motor stopped). or 2. Use the FWD/REV Key. or 3. Use Function
No. 1.02 to reprogram the forward and reverse direction.
6.4
MULTI-FUNCTION OUTPUT RELAY CONNECTION – The Multi-Function Output Relay Contacts
are located at TB2, as shown in Figure 12. The Multi-Function Output Relay is factory pro-
grammed to function as a “Run” relay (Function No. 5.00 set to “0000”). When the drive is put into
the Run Mode, the relay contacts will change state (the Normally Open (N.O.) contact will close
and the Normally Closed (N.C.) contact will open). See Table 5.
19
Normally Closed
Relay Common
Normally Open
Output Contacts
KBDA-27D, 29, 45, 48
NC
NO
TB2
COM
Normally Closed
Relay Common
Normally Open
Output Contacts
KBDA-24D
NC
NO
TB2
COM
Ground
3-Phase, 50/60 Hz
Motor
(Earth)
AC Line Input
V
U
L3
L2
W
L1
208/230, 400/460 Volt
TB1
MOTOR
AC LINE
Ground
Single-Phase, 50/60 Hz
(Earth)
208/230 Volt
L2
L1
L3
Wire the single-phase AC line input
to Terminals "L1" & "L2", as shown below.
Model KBDA-29 Only
AC Line Input
Notes: 1. Model KBDA-29 is rated for 2 HP maximum with single-phase AC line input and 3 HP maximum with 3-phase AC line input.
2. Models KBDA-29, 45, 48 contain AC Line Phase Loss Detection. (Model KBDA-29: when used on 3-phase AC line input set for 7.0 Amps
or higher (3 HP (2.25 kW)).
FIGURE 11 – MODELS KBDA-29
1
, 45
2
, 48
2
AC LINE INPUT, MOTOR, AND GROUND CONNECTIONS
FIGURE 12 – MULTI-FUNCTION OUTPUT RELAY CONTACTS
TABLE 5 – MULTI-FUNCTION OUTPUT RELAY “RUN” AND “FAULT” RELAY OPERATING MODES
Drive Operating Condition
Function 5.00 Set to “0000”
Function 5.00 Set to “0001”
“Run” Relay Mode
“Fault” Relay Mode
N.O. Contact
N.C. Contact
N.O. Contact
N.C. Contact
Power Off
Open
Closed
Open
Closed
Power On (Stop Mode)
Open
Closed
Closed
Open
Run Mode
Closed
Open
Closed
Open
All Faults
Open
Closed
Open
Closed