beautypg.com

Auxiliary equipment, Reset, Tb1 reverse/stop – KB Electronics KBDA-42 User Manual

Page 48: Forward/stop

background image

47

A6.

RESET

The Multi-Function Input Terminals can be used to reset the drive, after a fault has been cleared, by

connecting a switch or contact to any Multi-Function Input Terminal “1” – “7”, as shown in Figure 31.

Set the respective Multi-Function Input Terminal (Function Nos. 7.00 – 7.06), which will be used for

“Reset”, to “0009”. In Figure 31, Multi-Function Input Terminal “4” has been arbitrarily chosen.

FIGURE 30 – EXTERNAL FAULT AUXILIARY EQUIPMENT SWITCH OR CONTACT CONNECTION AND FUNCTION SETTING

TB1

15

11

6

18

3

2

1

16

17

4

5

19

20

23

8

7

21

22

9

10

24

25

28

13

12

26

27

14

Auxiliary Equipment

Function Setting

Function No.

Code

7.04

Multi-Function

Input Terminal 5

0008

External

Fault

FIGURE 31 – RESET SWITCH OR CONTACT CONNECTION AND FUNCTION SETTING

TB1

15

11

6

Reset

18

3

2

1

16

17

4

5

19

20

23

8

7

21

22

9

10

24

25

28

13

12

26

27

14

Function Setting

Function No.

Code

7.03

Multi-Function

Input Terminal 4

0009

Reset

FIGURE 29 – FORWARD/STOP-REVERSE/STOP SWITCH OR CONTACT CONNECTIONS AND FUNCTION SETTINGS

16

15

1

TB1

Reverse/Stop

26

21

18

17

2

3

20

19

5

4

6

23

22

7

8

25

24

10

9

11

14

28

27

12

13

Forward/Stop

Function Settings

Function No.

Code

1.00

Run/Stop-Forward/Reverse

Control

0001

External

Contacts

7.03

Multi-Function

Input Terminal 4

0006

Forward/Stop

Command

7.06

Multi-Function

Input Terminal 7

0007

Reverse/Stop

Command

A5.

EXTERNAL FAULT

The Multi-Function Input Terminals can be used to provide feedback to the drive when a fault condi-

tion occurs in auxiliary equipment. The connection to the Multi-Function Input Terminals is typically

from a normally open relay, contact, or PLC, as shown in Figure 30. When the circuit is closed, the

drive will “stop” and the display will show “EF-t”.

Set the respective Multi-Function Input Terminal (Function Nos. 7.00 – 7.06), which will be used for

“External Fault”, to “0008”. In Figure 30, Multi-Function Input Terminal “5” has been arbitrarily chosen.

This manual is related to the following products: