Start/stop, Close to start, open to stop) – KB Electronics KBDA-42 User Manual

Page 49

background image

48

FIGURE 32 – 2-WIRE START/STOP SWITCH OR CONTACT CONNECTION AND FUNCTION SETTINGS

4

Start/Stop

2

1

15

16

3

17

18

TB1

6

5

19

20

8

7

21

22

10

9

23

24

12

11

25

26

14

13

28

27

(Close to Start, Open to Stop)

Function Settings

Function No.

Code

1.00

Run/Stop-Forward/Reverse

Control

0001

External

Contacts

7.02

Multi-Function

Input Terminal 3

0010

Normally

Open Start

A7.

2-WIRE AND 3-WIRE START/STOP

A remote Start/Stop Switch or Contact can be used to start and stop the motor in lieu of the

RUN/STOP Key on the Keypad. The Start/Stop Switch or Contact can be connected for 2-Wire or 3-

Wire configuration, as described below.

2-WIRE START/STOP SWITCH OR CONTACT CONNECTION

2-Wire Start/Stop requires a maintained switch or contact. Connect the switch or contact to the

respective Multi-Function Input Terminal “1” – “7” and to Terminal “8” (common), as shown on Figure 32.

Set Run/Stop-Forward/Reverse Control (Function No. 1.00) to External Contacts (“0001”). Set the

respective Multi-Function Input Terminal (Function Nos. 7.00 – 7.06), which will be used for “Normally

Open Start”, to “0010”. In Figure 32, Multi-Function Input Terminal “3” has been arbitrarily chosen.

Note: Function code “0011” should not be programmed when using 2-Wire Start/Stop.

3-WIRE START/STOP SWITCH OR CONTACT CONNECTION

3-Wire Start/Stop requires momentary switches or contacts. Connect the normally open side of

the switch or contact to the respective Multi-Function Input Terminal “1” – “7”. Connect the normally

closed side of the switch or contact to the other respective Multi-Function Input Terminal “1” – “7”.

Connect the common of the switch or contacts to Terminal “8”. See Figure 33, on page 49.

Set Run/Stop-Forward/Reverse Control (Function No. 1.00) to External Contacts (“0001”). Set the

respective Multi-Function Input Terminal (Function Nos. 7.00 – 7.06), which will be used for “Normally

Open Start”, to “0010”. Set the respective Multi-Function Input Terminal (Function Nos. 7.00 – 7.06),

which will be used for “Normally Closed Stop”, to “0011”. In Figure 33, on page 49, Multi-Function

Input Terminals “1” and “2” have been arbitrarily chosen.

Notes: 1. When an MFIT (Terminal 2) is assigned code “0011”, the MFIT (Terminal 1) assigned code

“0010” automatically changes from maintained to momentary operation. 2. When using 3-Wire

Start/Stop, “Stop” will override “Start”, even if the Start Switch or Contact is kept in the “Start

position.