Note: (1) IODA Option Board required. (2) DIAC Option Board required.

KBDA PROGRAMMABLE FUNCTION SUMMARY LIST (REV. 100.1)

Function

Group No.

Description

0

Motor and Drive Parameters

1

Run/Stop Mode

2

Frequency Control

3

Drive Operating Parameters

4

Digital Display Modes

5

Onboard Multi-Function Output Relay Operating Mode

6

Drive Status and Reset

7

Multi-Function Input Terminals

(1)

8

Multi-Function Output Relays and Output Signal Operation

(1)

9

Analog Input Signal Operation

(1)

10

Communication Mode

(2)

11

Reserved Functions

PROGRAMMABLE FUNCTION GROUPS

Function

No.

Description

Range/Code

Factory

Setting

0.00*

Rated Motor Frequency (Hz)

0000: 60 Hz
0001: 50 Hz
0002: Special (Set by Function No. 0.05)

0000

0.01*

Motor Nameplate Current (Amps)

(1)

0.02*

Motor Type

0000: Inverter Duty, TEFC
0001: External Fan Cooled

0000

0.03*

Torque Mode

0000: Constant Torque (Machinery)
0001: Variable Torque (HVAC)

0000

0.04*

GFCI Operation

(2)

0000: GFCI Operation Disabled
0001: GFCI Operation with Standard GFCI
0002: GFCI Operation with Sensitive GFCI

0000

0.05*

Motor Frequency (Hz)

(3), (4)

30 – 240

60, 50

0.06*

Motor Nameplate Voltage (% Drive Output)

(5)

0 – 100.0

100

(6)

FUNCTION GROUP 0 – MOTOR AND DRIVE PARAMETERS

Notes: (1) Factory Setting is the drive rated output current. See Table 3, on page 10. This function is used to enter the Motor Nameplate

Rated Current, which allows proper operation of the I2t Motor Overload Protection. (2) GFCI operation overrides the Switching Frequency set

by Function No. 3.15. (3) When the drive is set for 50 Hz motors (Function No. 0.00 set to “0001”), the Motor Frequency factory setting will

automatically reset to 50 Hz. (4) The Motor Frequency for standard 50 Hz or 60 Hz motors is set by Function No. 0.00. For custom motors

(e.g., 100 Hz) set Function No. 0.00 to “0002” and Function No. 0.05 to the Motor Nameplate Rated Frequency. (5) This function is used for

motors with non-standard nameplate rated voltage (e.g., 80 Volts AC). (6) The factory set output of the drive is 100% of the AC line input

voltage. In 60 Hz Mode (Function No. 0.00 set to “0000”) the drive output will be 230 Volts, maximum, for 230 Volt motors and 460 Volts,

maximum, for 460 Volt Motors. In 50 Hz Mode (Function No. 0.00 set to “0001”) the drive output will be 220 Volts, maximum, for 220 Volt

motors and 400 Volts, maximum, for 400 Volt Motors.

* Functions which can only be changed while the drive is in the Stop Mode.