beautypg.com

Potentiometer main speed wiper low high – KB Electronics KBDA-42 User Manual

Page 53

background image

52

FORWARD MOTOR OPERATION

Analog Input 1 – Connect the potentiometer to Terminals “9” (+5 Volts), “19” (Analog Input 1), and

“20” (Common). Set Frequency Control (Function No. 2.00) to Analog Input 1 (“0002”).

Analog Input 2 – Connect the potentiometer to Terminals “9” (+5 Volts), “21” (Analog Input 2), and

“22” (Common). Set Frequency Control (Function No. 2.00) to Analog Input 2 (“0003”).

REVERSE MOTOR OPERATION

Analog Input 1 – Connect the potentiometer to Terminals “10” (-5 Volts), “19” (Analog Input 1), and

“20” (Common). Set Frequency Control (Function No. 2.00) to Analog Input 1 (“0002”).

Analog Input 2 – Connect the potentiometer to Terminals “10” (-5 Volts), “21” (Analog Input 2), and

“22” (Common). Set Frequency Control (Function No. 2.00) to Analog Input 2 (“0003”).

A11. MULTI-FUNCTION OUTPUT RELAYS

Two Multi-Function Output Relays are provided, which can be programmed for Run, Fault, Target

Frequency, Frequency Threshold Level (> 8.04 – 8.05), Frequency Threshold Level (< 8.04 + 8.05), I2t

or I•t Fault, Load Loss, External Fault, and Motor Overload. Relay 1 is factory programmed to operate

as a “Run” Relay (Function No. 8.00 set to “0000” (factory setting)). Relay 2 is factory programmed to

operate as a “Fault” Relay (Function No. 8.01 set to “0001” (factory setting)). The maximum allowable

contact load current is 2 Amps. See Figure 38, on page 53.

Note: If the drive “stops”, due to an External Fault Trip (“EF–t”), which indicates that a Multi-Function

Input Terminal (Function Nos. 7.00 – 7.06 set to “0008”) has closed, the Multi-Function Output Relay

Contacts will change state (when Function No. 8.00 or 8.01 is set to “0007”).

Multi-Function Output Relay 1 Contacts

Normally Open (N.O.) Contact: TB1 Terminal “23”.

Common (COM): TB1 Terminal “24” (contact common for Relay 1 only).

Normally Closed (N.C.) Contact: TB1 Terminal “25”.

FIGURE 37 – BIDIRECTIONAL MOTOR OPERATION MAIN SPEED POTENTIOMETER CONNECTION AND FUNCTION SETTING

4

3

1

2

TB1

15

16

17

18

8

7

6

5

19

20

21

22

12

11

10

9

23

24

25

26

14

13

28

27

Potentiometer

Main Speed

Wiper

Low

High

VOLT

CUR

MAX2

J1

Function Setting

Function No.

Code

2.00

Frequency

Control

0002

Analog

Signal 1

BIDIRECTIONAL MOTOR OPERATION (Use Analog Input 1 Only)

Connect the potentiometer to Terminals “9” (+5 Volts), “19” (Analog Input 1), and “10” (-5 Volts), as

shown in Figure 37. Set Frequency Control (Function No. 2.00) to Analog Input 1 (“0002”). In this

mode, the remote potentiometer is set for zero speed at 50% rotation. Rotating the potentiometer

clockwise will increase motor frequency in the forward direction. Rotating the potentiometer counter-

clockwise will increase motor frequency in the reverse direction.

This manual is related to the following products: