Securitron M380BD_C_C2_X MAGNALOCK_Series User Manual
Page 7
PN# 500-23310
Page 7
Rev. B 06/14
SW1
DIP Switch SW1.4:
PIR Ambient Light
Compensation
Can be enabled with
SW1.4
Ambient Light
Compensation Off
(default)
Position 4
Off
Position 4
OFF
Ambient Light
Compensation ON
Position 4
ON
Position 4
ON
SW1
DIP Switch SW1.5:
External PIR Input
External input at J6 can
be enabled at SW1.5
DISABLE External PIR
Input
Position 5 OFF (default)
ENABLE External PIR
Input
Position 5 ON
JP1
Jumper 1: Alternate
(REX) Output
A 3-pin jumper that
controls the output
setting for Alternate
(REX) Output at
Terminal Block J7.
(NC) Normally Closed
Circuit Closed, Circuit opens
when REX active (default
setting)
(NO) Normally Open
Circuit Open, Circuit closes
when REX active
JP3
Jumper 3:
BondSTAT
Mode Select
A 3-pin jumper that
controls the output
setting for the
BondSTAT in Terminal
Block J8 Position 1 & 2.
(NC) Normally Closed
Circuit Closed when Door is
Closed (default setting)
(NO) Normally Open
Circuit Open when Door is
Closed
JP4
Jumper 4:
Door Position
Mode Select
A 3-pin jumper that
controls the output
setting for the Door
Position Switch (DPS)
in Terminal Block J12
Position 1 & 2.
(NC) Normally Closed
Circuit Closed when Door is
Closed (default setting)
(NO) Normally Open
Circuit Open when Door is
Closed
J9
Terminal Block 9
Tamper Switch
A 2-wire terminal block providing a signal which changes
state as determined when the cover is sensed to be
removed. (Circuit is Normally Closed with cover in place).
J3
Terminal Block 3
Magnalock Input
Power
A 2-wire terminal block providing connection to a 12 or 24
VDC power supply for the main Magnalock operation.
Position 1 = (+) Positive. Position 2 = (-) Negative.
J2
Terminal Block 2
Auxiliary Input
Power
A 2-wire terminal block providing connection to the power
supply for the auxiliary components (PIR and/or Camera).
Position 1 = (+) Positive. Position 2 = (-) Negative.