beautypg.com

FEC AFC1500 User Manual

Page 44

background image

Termination
Termination of the CCLink requires a terminating resistor at each end of the
fieldbus. Connect 120 ohm resistor between the DA & DB terminals if this is
the last connection. (Remember that the CCLink master also needs to be
terminated)

I/O addressing set by PLC TO / FROM
commands in Logic

I/O Configuration*

128 inputs, 128 outputs max. Size set
in groups of 32 I/O (Occupied Stations)

Maximum Cyclic I/O Size

HDLC Standard

Transmission Format

Master/Slave - EIA RS485

Communications Type

Shielded Copper Twisted Pair
Mitsubishi BA1SJ61-(m) m=Meters
Belden 8102 or equivilent

Cable

1200m max. at 156K baud / 50m max.
at 10Mbit/s

Distance

64 Max.

Stations

156K - 10M baud - selectable

Speed

CC Link Specifications

* Actual I/O addressing must be assigned in the PLC logic. See the
Mitsubishi User Manual # 13J872 Control & Communication - Link System
Master / Local Module for logic reference. (Ref. Section 10)

Field Ground

FG

Pin 5

Connect cable shield

SHIELD

Pin 4

Digital Ground

DG

Pin 3

Communication Line

DB

Pin 2

Communication Line

DA

Pin 1

CC-Link connector

Connector: 5.08mm BU04/5 Hartmann or Equivalent

Wiring of the CC-Link network should be performed by using the cable listed
above in the CC-Link Specifications. The three twisted conductors should be
wired in series to each CC-Link device, using a terminating resistor at the
Master end and on the last Remote/Local device between the DA & DB
terminals. Connection should be DA to DA, DB to DB, DG to DG with the
cable shield connected to the SHIELD terminal. The field ground (FG) should
be connected to earth ground.

Chapter 3: Control Interfaces

44