beautypg.com

Teledyne 2010A - Split architecture thermal conductivity analyzer User Manual

Page 89

background image

Thermal Conductivity Analyzer

Part II: Analysis Unit

Teledyne Analytical Instruments

Part II: 2-3

NOTE:

The sample-line pressure regulator should be installed as
close to the sample point as possible to minimize sample-
line lag time.

NOTE:

An additional option is available for SEALED reference
application. This option would not have the reference Gas
Flow Meter, Piping and Fittings.

2-4

Pressure and Flowrate Regulation

Appropriate pressure reducing regulators must be installed at all gas

supply sources. To minimize flowrate adjustments the pressure regulators on
the supporting gas supply cylinders should be adjusted to provide the same
output pressure as the sample line regulator.

The gas pressure input should be reasonably well regulated. Pressures

between .35 and 3.5 bar (5- 51 psig) are acceptable - .7 bar (10 psig) is
normal as long as the pressure, once established, will keep the flow con-
stant
during analysis and within 50-200cc/min (between 0.1 and 0.4 scfh)
See Note.

Note: Gases lighter than air have a flowrate higher than indicated on

the flowmeter, while gases heavier than air have a flowrate
lower than indicated. Values can range from one half to twice
the indicated flowrate.

For example: For hydrogen or helium, set the flowrate to 0.1
scfh (50 cc/min). For carbon dioxide or argon, set the flowrate
to 0.4 scfh (200 cc/min).

When installing pressure regulators on supply cylinders, crack the

cylinder valves so that gas is flowing during installation. This will eliminate
the most common cause of standardization-gas contamination: air trapped
during assembly diffusing back into the cylinder. This procedure is particu-
larly important in applications where impurity content of 1 to 2 % is the
range of interest.

2-5

VENT Exhaust

There are two separate VENT fittings—one for the sample gas and one

for the reference gas

.

Use

1

/

4

inch tubing for both sample and reference vents

to minimize back pressure from restricted flow.

Exhaust connections must be consistent with the hazard level of the

constituent gases. Check local, state, and federal laws, and ensure that the
exhaust stream vents to an appropriately controlled area if required. If not