beautypg.com

Teledyne 2010A - Split architecture thermal conductivity analyzer User Manual

Page 32

background image

Teledyne Analytical Instruments

3 Installation

Model 2010A

3-0 Part I

Table 3-4: Required Rs-232 options

Parameter Setting

Baud 2400

Byte 8 bits

Parity none

Stop Bits 1

Message Interval 2 seconds

3.3.9 Remote Probe Connector

The 2010A is a single-split configuration analyzer, the Remote Probe

connector is used to interface the Analysis Unit. See Figure 3-6.

Figure 3-: Remote Probe Connector Pinouts

The voltage from these outputs is nominally 0 V for the OFF and

15 V dc for the ON conditions. The maximum combined current that can be

pulled from these output lines is 100 mA. (If two lines are ON at the same

time, each must be limited to 50 mA, etc.) If more current and/or a different

voltage is required, use a relay, power amplifier, or other matching circuitry

to provide the actual driving current.

In addition, each individual line has a series FET with a nominal ON

resistance of 5 ohms (9 ohms worst case). This could limit the obtainable

voltage, depending on the load impedance applied. See Figure 3-7.