Boiler will not maintain pressure

1. Check oil supply in the supply tank. Check for

clogged nozzle. Clean or replace it. Check oil filter and

replace if necessary.

2. Check gas supply.

3. The flue is too dirty. Clean it.

4. Check the steam pressure switch, reset it if

necessary.

5. Steam is overloaded, reduce it.

Water pump does not start or stop manually

1. Check the connection of water probe.

2. Check and clean the water probe.

3. Check the water level relay, if necessary replace it.

Low water alarm/burner shut off will not act in time

1. Check for tightness and clean the connections.

2. Clean or replace the dirty probes.

3. Replace the water level relay.

4. Check the tightness of the earth connection.

Starting the boiler, the high limit steam pressure

limit is illuminated and the burner stops

1. Boiler is completely filled with water, blow down the

boiler to normal water level.

2. On/Off pressure switch has failed; check the reading

on the pressure gauge.