The Fulton Companies*FB-S Series Manual*Version 2010-0820 rev. 3/5/13

Page 38

Note

Boiler may be supplied with PID type pressure controls in lieu of on/off and

high/low pressure switches.

g) Burner Programmer

i. Is located in the center of the control panel. Acts in conjunction with a

sensing device to ‘supervise’ the ignition sequence, prove the flame is

satisfactory and finally ‘monitor’ the established flame.

Should any fault occur, either during the ignition sequence or during

normal running, the programmer will immediately go to ‘lock-out’ and both

main and pilot gas/oil valves will shut to isolate the fuel line

to the burner. Lockouts include high steam pressure, low water, high/low

gas pressure and flame failure.

h) Flame Failure Indicator

i. Indicates the burner combustion control relay, detects a flame failure

condition.

2. Burner

Fulton Boiler FB-S model can mount with gas burner, oil burner or dual fuel burner

on customer’s request. See specific Burner Manual fro details.

Oil Burner

The fuel for the oil burner is from No.2 to No. 6 oil. The standard light oil burner for

a Fulton boiler is No.2 oil. The heavy oil burner can be used for No.4 to No.6

oil.

Modulating Control

Operating Limit

High Limit w/
Manual Reset