beautypg.com

Fulton FB-S Horizontal Firetube Boiler User Manual

Page 27

background image

The Fulton Companies*FB-S Series Manual*Version 2010-0820 rev. 3/5/13

Page 27

Example: From the chart we can see that a ¾” line that is 80’ in length can supply

118,000 BTU/hr.

10. Oil Supply

a) The oil supply piping to the boiler must be appropriate to local conditions

and must be constructed and installed in compliance with appropriate

Codes and Standards. It should be of sufficient size to satisfy the

pressure and volume flow requirements of the burner under all firing

conditions. Checks should be made to ensure that all meters and

other components are appropriately rated for the maximum oil flow

rate anticipated. Galvanized steel pipe should not be used. The supply

piping should include an appropriate filter.

b) A two-pipe system must be used between oil storage tank and the

burner. One for oil supply and one for oil return. A circulating oil pump is

required to deliver fuel oil at 1-3 psig from the storage tank to the burner.

A oil filter must be installed before the oil-circulating pump,

recommend less than 60 Mesh.

c) The final connection to the oil pump inlet should be made using the

flexible pipes supplied with the burner.

d) One gate valve should be installed to the inlet and outlet of the

circulating pump separately. A pressure gauge (0-60psi) should be

added to the outlet.

e) It is important to ensure that the return pipe is not obstructed as this

may result in damage to the pump.

f) In the case of heavy oil (No.4, No.5, and No.6 oil) the piping and oil

storage tank should be insulated, trace heated and thermostatically

controlled.

11. Installation Check Points-Refer to the details in the BURNER section

a) Make sure that all piping connections are complete and tight.

b) Make sure the pressure controls are adjusted properly.

c) Make sure all electrical connections in the control box, the water column,

and elsewhere are secure.

d) Make sure there is adequate boiler room ventilation. Combustion air

contaminates can cause damage to the boiler jacket and burner.

e) Before operating pumps, metering heads and compressors, make

certain that reservoirs are properly filled with the specific lubricant.