beautypg.com

Fulton FB-S Horizontal Firetube Boiler User Manual

Page 47

background image

The Fulton Companies*FB-S Series Manual*Version 2010-0820 rev. 3/5/13

Page 47

temperature and by the heat transfer rate and gas temperature. The tube temperature lies

between the shell and furnace temperature, but is nearer the shell temperature. Since all

these components are virtually the same length, they expend longitudinally by different

amounts causing mechanical and thermal stress. Whilst this is catered for in mechanical

design of the pressure vessel, the life expectancy of the boiler can be affected if the boiler

is frequently heated to quickly from cold. When starting from cold the furnace approaches

its design temperature shortly after start-up, whereas the tube and shell temperatures are

delayed by the time taken to bring the contained water up to temperature. As a result, the

thermal expansion is at its greatest. Additionally, the temperature gradient which exists

between the bottom and the top of the boiler is exaggerated. This can be

reduced by blowing the boiler down during the heat-up period. In practical terms, the ideal

solution would be to gradually raise the temperature and pressure in the boiler

progressively by firing the boiler on low fire for a few minutes and leaving it to ‘soak’ (e.g.

allowing the temperatures in the boiler and water to even out by diffusion) for 20 to 30

minutes, blowing down the boiler, firing the boiler again for a little longer and soaking for

less, and so on. If the boiler has been fired the day before, the large thermal mass in the

boiler will maintain the internal temperature to a point that the boiler can be simple switched

on (preferably on low fire) and then left to reach working temperature/pressure. The life

expectancy of the boiler and door insulation, ignoring other factors, is proportional to the

number of the thermal/mechanical cycles that the boiler undergoes from cold/zero pressure

to working temperature and pressure. A boiler that is continually maintained at working

pressure will last longer than one that is constantly heated and cooled.

Service Inspection of Weld Joints

The frequency of the safety requirement for in service inspection of the main welded joints

of the boiler is calculated by the number of cycles since the last inspection. Boilers running

twenty four hours a day require the shell and furnace end plate welds to be inspected at

intervals specified by local boiler codes. Boilers that are continually heated and cooled

require more frequent inspection. The purpose of the in-service weld inspections is to check

for:

i.

Buried defects during manufacture that are outside acceptable limits.

Because the boiler was 100% tested during manufacture none should be

found, and upon proof of 100% manufacturer testing these tests may be

waived at the discretion of the ‘competent person’.

ii.

Cracks propagating from region of the toe of the fillet weld on the shell to

the tube plate weld, resulting from fatigue or corrosion fatigue cracking.