e) Oil Pre-heater Tank (for heavy oil burners)

i. The oil preheater tank is mounted on the heavy oil burner ahead of the fan

housing. Its function is to preheat the oil to correct temperature. The unit is

equipped with three thermostats, ‘low temperature’ ‘operating’ and ‘limit’. A

thermometer and hot oil filter are mounted together as one unit on the

top left-hand side of the preheater tank viewed from the rear of the

burner.

f)

Air Pressure Switch

i.

Each of the gas burners is mounted on an Air Pressure Switch on the

burner scroll. Lack of combustion air, or insufficient air pressure, will stop

the switch completing the circuit, preventing the burner from operating.

g) Air Control

i. The Air Control System of the gas burners is similar to that of the oil

burners. The servomotor is mounted on the rear of the air inlet of the

burner and directly coupled to the air damper blade. This system

monitors and controls the combustion air entering the burner on

the requirement of the boiler heating during operating. The servomotor has

been adjusted by the manufacturer before the boiler delivery, so normally

the customer needn’t set it again.

h) Gas Train Assembly

i. Consist of pilot and main supply line, each line having a manual cock, a

governor, solenoid operated valves and two-air pressure switch (high and

low). The governors maintain a constant pressure of fuel entering the

burner and are adjustable. The solenoid valves are electronically controlled

by the burner programmer. For specific details, consult the burner

manufacturer’s instruction manual.