The Fulton Companies*FB-S Series Manual*Version 2010-0820 rev. 3/5/13

Page 37

100mm diameter standpipes mounted on top of the boiler center line

towards the front of the boiler. A standard boiler is fitted with Feedwater

pump On/Off, 1

st

Low Water, 2

nd

Low Water and High Water probes.

Note

If the Level Control System is a float type or pressure differential transmitter,

then refer to specific spec sheets located in this manual.

f)

Steam Pressure Controls

i. Three steam pressure controls are mounted on the side of the boiler near

the control panel. These are as follows:

a. Operating Control Pressure On/Off Switch. Controls the

on/off cycle of the boiler, switching the burner off when

the desired steam pressure is reached and switching it

on when steam pressure falls.

b. High Limit Switch. Should the Control Pressure Switch

fail, the steam pressure will raise above

the pre-set limit causing the High Limit Switch (set a

least 0.5 {3-4 psig} bar higher than the Control

Pressure Switch) to switch off and lock out the burner. A

High Limit Indicator will illuminate and an alarm will sound.

c. Modulating Pressure Switch. Switches the burner from high

to low flame and vice-versa as steam pressure/water temp

increases or decreases from setpoint.

2

nd

LWCO

Pump On

1

st

LWCO

Pump Off

High Water