The Fulton Companies*FB-S Series Manual*Version 2010-0820 rev. 3/5/13

Page 26

c) The gas supply piping to the boiler must be appropriate to local

conditions and must be constructed and installed in compliance

with appropriate Codes and Standards. It should be of sufficient size

to satisfy the pressure and volume flow requirements of the burner

under all firing conditions. Checks should be made to ensure that all

meters and other components are appropriately rated for the maximum

gas flow rate anticipated.

Note

It is essential that a manual isolation valve is fitted upstream of the gas

control train to allow the burner to be isolated for maintenance. The size of

this valve should not be less than that of the burner control train in order to

avoid any restriction in gas flow.

Warning

It is essential that the installation of the gas piping must be undertaken

only by suitably qualified and experienced personnel and in compliance

with appropriate Codes and Standards. The Fulton Companies can accept

no responsibility for consequential loss, damage or personal injury, which

results from a failure to follow the manual.

Gas Line Sizing Chart

*There is a more exact formula, but you can round off the conversion of CF to BTU by using 1=1000 (for

example 174 CF on the chart would be equal to 174,000 BTU). This will give a more conservative total

estimate.

Pipe

Size

Length of Pipe in Feet

Inches

10

20

30

40

50

60

70

80

90

100

½

174

119

96

82

73

66

61

56

53

50

¾

363

249

200

171

152

135

127

118

111

104

1

684

470

377

323

286

259

239

222

206

197

1 ¼

1404

955

775

663

588

532

490

456

428

404

1 ½

2103

1445

1161

993

880

795

734

688

641

605

2

4050

2784

2235

1913

1696

1538

1413

1315

1234

1165

2 ½

6455

4437

3503

3049

2703

2449

2253

2096

1966

1857

3

11,412 7843

6299

5391

4778

4329

3983

3705

3476

3284