Fulton FB-S Horizontal Firetube Boiler User Manual
Page 26

The Fulton Companies*FB-S Series Manual*Version 2010-0820 rev. 3/5/13
Page 26
c) The gas supply piping to the boiler must be appropriate to local
conditions and must be constructed and installed in compliance
with appropriate Codes and Standards. It should be of sufficient size
to satisfy the pressure and volume flow requirements of the burner
under all firing conditions. Checks should be made to ensure that all
meters and other components are appropriately rated for the maximum
gas flow rate anticipated.
Note
It is essential that a manual isolation valve is fitted upstream of the gas
control train to allow the burner to be isolated for maintenance. The size of
this valve should not be less than that of the burner control train in order to
avoid any restriction in gas flow.
Warning
It is essential that the installation of the gas piping must be undertaken
only by suitably qualified and experienced personnel and in compliance
with appropriate Codes and Standards. The Fulton Companies can accept
no responsibility for consequential loss, damage or personal injury, which
results from a failure to follow the manual.
Gas Line Sizing Chart
*There is a more exact formula, but you can round off the conversion of CF to BTU by using 1=1000 (for
example 174 CF on the chart would be equal to 174,000 BTU). This will give a more conservative total
estimate.
Pipe
Size
Length of Pipe in Feet
Inches
10
20
30
40
50
60
70
80
90
100
½
174
119
96
82
73
66
61
56
53
50
¾
363
249
200
171
152
135
127
118
111
104
1
684
470
377
323
286
259
239
222
206
197
1 ¼
1404
955
775
663
588
532
490
456
428
404
1 ½
2103
1445
1161
993
880
795
734
688
641
605
2
4050
2784
2235
1913
1696
1538
1413
1315
1234
1165
2 ½
6455
4437
3503
3049
2703
2449
2253
2096
1966
1857
3
11,412 7843
6299
5391
4778
4329
3983
3705
3476
3284