Specifications and dimensions, Specifications, Maximum fuel consumption – Fulton FB-S Horizontal Firetube Boiler User Manual
Page 16: Connection

The Fulton Companies*FB-S Series Manual*Version 2010-0820 rev. 3/5/13
Page 16
2. Specifications and Dimensions
Specifications
Model FB-S
100
125
150
200
250
300
400
500
650
800
Nominal steam output
(lbs/h) (1)
3450
4312
5175
6900
8625
10350
13800
17250
22425
27600
Design pressure (psig)
15/150
15/150
15/150
15/150
15/150
15/150
15/150
15/150
15/150
15/150
Water Volume (gallons)
779
924
924
1294
1585
1849
3594
4650
4677
5265
Maximum fuel consumption
(2)
Light Oil (gp/h)
29
36
43
58
73
88
117
146
189
234
Heavy Oil (gp/h)
27
34
41
54
68
82
108
136
177
216
Natural Gas (ft
3
/h)
4156
5196
6235
8313
10,392
12,470
16,626
20,784
27,019
33,252
Note:
(1) All steam output lbs/hr ratings from 0 psig at 212F.
(2) Fuel consumption based on light oil 1, 40,000 BTU/gal, natural gas 1000 BTU/ft
3
, heavy oil 160,000
BTU/gal.
Connection
Model FB-S
100
125
150
200
250
300
400
500
650
800
Main steam valve (150 psig)
Flange
2.5
3
3
4
4
4
6
6
6
8
Safety valve connections
(150 psig) (in)
2
1.5 (2)
1.5 (2)
2 (2)
2 (2)
2.5 (2)
2.5 (2)
4
4 (2)
4 (2)
Main steam valve (15 psig) (in)
Consult Factory
Safety valve (15 psig) (in)
Consult Factory
Feed Water inlet line (in)
1.0
1.25
1.25
1.25
1.25
1.5
1.5
2
2
2
Blowdown line (in)
1.5 (2)
1.5 (2)
1.5 (2)
1.5 (2)
1.5 (2)
1.5 (2)
1.5 (2)
2 (2)
2 (2)
2 (2)
Flue diameter (in)
14
16
16
18
20
20
22
22
26
26
Note: Specifications and dimensions are approximate. Fulton reserves the right to change specifications and
dimensions.