Fulton FB-S Horizontal Firetube Boiler User Manual
Page 46

The Fulton Companies*FB-S Series Manual*Version 2010-0820 rev. 3/5/13
Page 46
Note
If the 2
nd
Low Water and High Pressure Alarm/Reset switch illuminate and
the alarms sound, check that the burner mounted Burner On/Off/Reset
Switch is in the OFF position, and then reset both alarms by pressing the
switches
Note
It may be necessary to vent the feed water pump by bleeding air from the
plug mounted in the top casting below the pump motor to pump body
connection
2. Starting the Burner From Cold
a) Fill the boiler as described in Section 1.
b) SHUT the main steam valve.
c) Open all the valves in the gas train/oil supply. It is assured that the fuel supply
lines have been purged prior to attempting to start the boiler/burner.
d) Switch the Burner On/Off/Reset Switch to the ON position. The 2
nd
Low Water and
High Pressure Alarm/Reset switches will illuminate and alarms will sound due to
the power restoration interlock.
e) Reset the alarm by pressing both switches. If the 2
nd
Low Water alarm cannot be
cancelled, check the water level in the sight glass.
f)
The burner motor will start and, after going through post purge/ pre purge interlock
checks, should fire after approximately 45 seconds.
Note
Before leaving the boiler unattended, the daily operating tests should be
carried out to check the functions of all the safety interlocks. For more
detailed information on the burner firing sequence consult the burner
manufacture’s Operation and Maintenance instructions.
Practical Considerations
When starting up the boiler, it is prudent to minimize the thermal and mechanical stress
caused by differential expansion of various parts of the boiler as they reach working
temperature. The temperature of the shell is determined by the contained water/steam