42
8-7 RS422 Card Wiring
This option has a subminiature D, 37 pin, fe-
male connector and is wired as a DCE (Data
Communications Equipment) device. It is de-
signed to be connected to a DTE (Data Termi-
nal Equipment) device. If it must be con-
nected to a DCE device, it will be necessary
to cross wires 4 and 6 as well as 22 and 24 at
one end of the connector harness.
8-7.1 Wiring Diagram RS422 / Strobe (37 Pin
Connector)
8-7.2 RS422 Wiring Notes
The Batcher requires only four wires for
RS422 communication:
a) Pin 22 (Receive Data +A)
b) Pin 4 (Receive Data -B)
c) Pin 24 (Transmit Data +A)
d) Pin 6 (Transmit Data -B)
Other pins are jumped to simulate appropriate
responses required for some terminals.
a) Pins 7, 25 (Request To Send), Pins 9,
27 (Clear To Send). Jumped internally
to echo back signals.
b) Pins 11, 29 (Data Set Ready), Pins 13,
31 (Received Line Signal Detector),
Pins 12, 30 (Data Terminal Ready).
Jumped internally to echo back signals.
8-8 Strobe Input Electrical Requirements
Both the RS232 and RS422 interface option
cards have inputs that allow data to be re-
quested over a separate strobe input and a 3
bit, data request, code input. Any number of
unit's, data request, code lines can be linked
in parallel; as long as the source can drive the
combined load of all inputs linked together
(1.5 K Ohm divided by the total number linked
together). Data is transmitted over the serial
lines using standard RS232 or RS422 charac-
teristics.
Note: Strobe and data request inputs are
positive true with signal ground as reference:
8-8.1 Strobe Input Levels
0 or low: Open or 0 to 1 VDC
1 or high: 3 to 30 VDC
Impedance: 1.5 K Ohm