Liquid Controls SP2800 User Manual
Page 42
38
7-2.3 Calculating the K Factor for Analog
Inputs.
Step 1.
Find out what value the maximum
input signal represents. This
should be specified on your device
or with its paper work.
Example #1: 20 mA = 100 gal / min
Example #2: 5 V = 10 ft / sec
Example #3: 10 V = 32 m
3
/ hr
Step 2.
The Rate K Factor is equal to
10000 divided by the value from
Step 1.
Example #1:
Base K Factor = 10000
÷
100 = 100
Example #2:
Base K Factor = 10000
÷
10 = 1000
Example #3:
Base K Factor = 10000
÷
32 = 312.5
Step 3.
Enter the Rate K Factor.
(See Section 3-3, Menu Item 3).
Step 4.
Modify the Rate K Factor to make
the time conversion to seconds for
the count display. This is done by
dividing the Rate K Factor by the
Time Conversion Factor. If no con-
version is necessary skip this step
and let the Rate K Factor be the
same as the Count K- Factor. USE
THE TIME CONVERSION CHART
AS NEEDED.
Example #1:
Convert pounds per min to pounds per sec
Count K Factor = 100
÷
0.01666667 = 6000
Example #2: No conversion needed.
Count K Factor =1000
Example #3:
Convert gal per hr to gal per sec.
Count K Factor = 312.5
÷
0.0002778 = 1124910
Step 6. Enter the Count K Factor. (See
Section 3-3, Menu Item 3)
7-2.4 Analog K Factor Formulas.
10000 = Rate K Factor
Maximum Input Signal
Rate K Factor = Count K Factor
Time Conversion Factor
Q. Is it possible to count in one system of
measurement and display rate in another?
A. Yes, modify the Count K Factor to reflect
any units conversions. This is done by divid-
ing the Count K Factor by another Units Con-
version Factor. REFER TO THE UNITS
CONVERSION CHART AS NEEDED.
UNITS CONVERSION CHART
To convert:
divide by
To convert:
divide by
ft to m
0.3048
kg to lb
2.2046
ft
2
to m
2
0.0929
l to ft
3
0.0353
ft
3
to m
3
0.02832
l to gal
0.2642
ft
3
to gal
7.4805
m to ft
3.2808
gal to l
3.7854
m
2
to ft
2
10.7639
gal to m
3
0.00379
m
3
to ft
3
35.3147
gal to ft
3
0.1337
m
3
to gal
264.172
gal to lb(H
2
O)
8.3378
lb to kg
0.45359