3-10 Setup Procedure For The Batcher (continued)

MENU ITEM 10 16 POINT

This section is for models of the Batcher which have 16 Point Linearization. This option
allows the user to key in from 3 to 16 different frequency points (inputs per second) and
assign different K Factors dividers from 0.00011 to 999999 for each of these frequen-
cies.

Please refer to the K Factor worksheets (Section 7) or other notes you may have prepared.

PRESS

DISPLAY

PRESET

↓↓↓↓↓

PREWARN

↓↓↓↓↓

Press until . . .

16 POINT

↓↓↓↓↓

SECONDS

↓↓↓↓↓

D

MINUTES

↓↓↓↓↓

D

HOURS

↓↓↓↓↓

The unit calculates the base rate per second from the incoming frequency and the
specified K Factor. The rate can then be displayed in 3 ways:
SECONDS: The base rate.
MINUTES: The base rate times 60.
HOURS: The base rate times 3600.

TEST

↓↓↓↓↓

TEST is used to help set up the points and K Factors. In this mode the K Factor is
automatically set to (1) one for both rate and total for all 16 points. Further information
on this mode can be found in Section 7-3 of this manual.

POINT 00

Press ENT on desired rate display. The unit now enters the Frequency and K Factor
setup mode.

To escape from this mode, press ENT when POINT 00 is being displayed.
Enter any other point from 1 to 16 via the front keypad and press ENT to continue.
Note: If the point number entered is greater than 16, the unit will default back to point
16.