3.3 Automatic Open / Close Limit Adjustment

Gate MUST open until it contacts the physical “open” stop. (if gate starts to close, turn power off and
change the direction operator opens (SW 1, switch 1). Turn power back on and give open command again).

Auto-close timer will close the gate until it contacts the physical “close” stop. (Manual close command
required if timer is turned off).

Gate will automatically open until it gets approximately 12 inches away from the full open position and
stop, then continue opening until it contacts the physical “open” stop again.

Auto-close timer will close the gate until it gets approximately 12 inches away from the full close position
and stop, then continue closing until it contacts the physical “close” stop again. (Manual close command
required if timer is turned off).

Sequence of Automatic “Multiple Gate Cycles” to Set Gate Limits

Open

Open

Close

Close

Sequence

Finished

After the first open command is given to the operator

(gate can be in any position)

:

Open and close gate positions are now set and will be remembered by the 9100 (until it loses AC power).
Gate will function normally after automatic “Multiple Gate Cycles” sequence has finished.

The 9100’s open/close limits DO NOT have to be physically adjusted. Every time the 9100 is powered up, the first open
command will automatically run “Multiple gate cycles” that will locate and remember the gate’s open and close positions.

These positions are determined by the physical stops that have been installed (See section 1.2, page 10).

Timer:

The Auto-Close Timer should be turned ON (SW 1, switch 2) to allow the “multiple gate cycles” to run automatically,

otherwise manual close commands will be required to complete this sequence.

Clutch:

The clutch’s factory setting will work correctly for most installations. The clutch must NOT slip while the gate is cycling

between the full open and full closed position or the gate limits will be incorrect. If the clutch slips during this period, it must be
tightened before running this sequence (See section 3.4 on the next page).

Safety Devices:

Run this sequence before testing any safety features (primary inherent reverse sensor, secondary entrapment

protection, entrapment alarm and reset features).

Reversing Edge mounted on the Gate using End Posts:

When using a reversing edge on either end of the gate with an end

post as the physical stop, the reversing edge must be disconnected from the circuit board everytime this sequence will be run
(the UL 325 terminal can be unplugged from the circuit board).

CAUTION: Keep pedestrians and vehicles clear of the gate while this sequence is running!

Note: If gate encounters an obstruction during this sequencing,
it will automatically continue after obstruction has been cleared.

“Multiple Gate Cycles”