2 continued, Sw 2 (right 8 switches) – Controlled Products Systems Group 9100-080 User Manual
Page 25
9100-065-Z-3-13
23
OFF
ON
Operator Model
Select
5
7-OFF
7-OFF
7-ON
7-ON
8-OFF
8-ON
8-OFF
8-ON
Gate Close
Back-Off
Position
Normal Setting. Gate fully closes.
Gate stops short 1” from full close position. Used for a reversing edge device.
Gate stops short 2” from full close position. Used for a reversing edge device.
Gate stops short 3” from full close position. Used for a reversing edge device.
3.2 Continued
Switch
Function
Setting
Description
SW 2 (Right 8 Switches)
2
7 and 8
Built-in
Solenoid
Lock
OFF
ON
4
Normal Setting. Fail-safe logic. Lock engages only if attempt is made to force gate
open (Factory setup).
Fail-secure logic. Lock engages after each gate cycle (2600-862 Lock kit required).
Normal Setting. Switch must be OFF for Model 9100.
DO NOT use ON setting for Model 9100.
OFF
ON
Partial Open
(14 Ft)
3
Normal Setting. Switch must be OFF for terminal #5 input to open gate 14 Ft.
DO NOT use ON setting. NOT associated with partial open feature for the 9100.
OFF
ON
OFF
ON
Normal Setting. Input to terminal #6 and/or reverse loops will reverse gate
during close cycle.
Input to terminal #6 and/or reverse loops will stop gate during close cycle – gate
will continue to close after input to terminal #6 and/or reverse loops are cleared
(Helps prevent tailgating vehicles from unauthorized entry).
OFF
ON
6
Normal Setting. Timer will function normally.
Opening gate will stop and begin to close as soon as all reversing inputs (Reverse
loops, photo sensors) are cleared regardless of the distance the gate has opened.
1
SW 2 Switch 1
Switch 1 ON, plug-in exit loop detector is a normal full open input. Switch 1 OFF, the normal exit loop port
function is bypassed and a jumper wire is needed to open and close gate(s) for certain applications (Single operator automatic
exit loop partial open or dual operator application) depending on the type of loop detector used and position of jumper wire.
SW 2 Switch 2
Determines if an input to terminal #6 (Photo Sensors) AND/OR reverse loops will reverse OR stop a CLOSING gate.
A tailgating vehicle can activate terminal #6 (Photo sensors) and/or reverse loops while the gate is in the closing cycle from the
previous vehicle’s authorized entry:
If switch 2 is turned OFF (Reverse), the closing gate that gets activated by a tailgating vehicle will reverse back to the open
position, possibly allowing the tailgating vehicle unauthorized entry while the gate is reversing back to the open position.
If switch 2 is turned ON (Stop), the closing gate that gets activated by a tailgating vehicle will stop, partially or completely
blocking the pathway, NOT allowing the tailgating vehicle to enter without proper authorization. The gate will not move until all
sensors are clear, usually forcing the tailgating vehicle that activated the sensors to back away from the gate. The gate will then
continue until closed, helping prevent the tailgating vehicle from unauthorized entry.
SW 2 Switch 3
Switch must be in the OFF position. Inputs connected to terminal #5 will open and reverse the gate only 14 Ft.
SW 2 Switch 4
This switch determines the operation of the built-in solenoid lock. The OFF setting is the factory setup. Caution:
Do not set this switch to ON unless the 2600-862 fail-secure manual release kit has been installed in the operator.
Changing this switch to the ON setting without installing the lock kit will damage the operator. See pages 36 and 37 for more
information about Fail-Safe vs. Fail-Secure release systems.
SW 2 Switch 6
Turning the quick-close feature on will cause the auto-close timer to close the gate after 1 second, regardless of
the setting of the auto-close timer potentiometer. This will also cause an opening gate to stop and reverse when the reverse
loops and/or photo sensors are cleared. This feature, along with turning SW 2, switch 2 ON above, is useful to help prevent
tailgating vehicles from unauthorized entry.
SW 2 Switches 7-8
These work in conjunction with each other and determine if the operator will stop the gate at the full close
position, or if the gate should stop 1, 2 or 3 inches short of the full close position. Needed only when using a reversing edge
entrapment protection device on the closing edge of the gate with an end post as the physical stop.
Quick-Close
Timer Override
Exit Loop Port
Output
Jumper
Wire
Needed
Full Open Input
A plug-in exit loop detector plugged into the EXIT Loop port will partially open single
operator or fully open dual operators depending on type of loop detector used).
Normal Setting. Plug-in exit loop detector will fully open gate (Single operator).
Reverses Gate
Stops Gate